Brockenbrough_Ch06.qxd  9/29/05  5:15 PM  Page 6.6



                                                 DESIGN OF BUILDING MEMBERS


                   6.6  CHAPTER SIX

                                 Because

                                               KL  =  19  ×12      E      29 000      
                                                                               ,
                                                                 .
                                                                          .
                                               r  225  = 101 3 .    ≤  471  F y  = 471  36  = 133 7 .   
                                                                
                                                    .
                               The elastic critical stress, from Eq. (6.8), is
                                                            π 2  × 29 000
                                                                 ,
                                                        F =          = 27 87 ksi
                                                                        .
                                                         e
                                                              101 3 .  2
                               Equation (6.9) yields the critical stress
                                                      F cr = (0.658 36/27.87 ) × 36 = 20.97 ksi
                               The design strength of the 6-in pipe, then, from Eqs. (6.6) and (6.7), is
                                             φP n = 0.90 × 5.58 × 20.97 = 105.3 kips > 93.6 kips  OK

                   6.6 EXAMPLE—LRFD FOR WIDE-FLANGE SECTION
                   WITH AXIAL COMPRESSION

                               A wide-flange section is to be used for columns in a five-story steel building. A typical interior
                               column in the lowest story will be designed to support gravity loads. (In this example, no eccentricity
                               will be assumed for the load.) The effective height of the column is 18 ft. The axial loads on the column
                               from the column above and from the steel girders supporting the second level are dead load 420 kips
                               and live load (reduced according to the applicable building code) 120 kips.
                                 The factored axial load is the larger of the following:
                                                P u = 420 × 1.4 = 588 kips
                                                P u = 420 × 1.2 + 120 × 1.6 = 696 kips  (governs)
                                 Use of the column design tables of the AISC “Manual of Steel Construction” presents the fol-
                               lowing options:
                                 For a column of A36 steel, select a W14 × 99, with a design strength φP n = 745 kips.
                                 For a column of A992 steel, select a W12 × 87, with a design strength φP n = 758 kips.
                               Both steels cost about the same, so the W12 × 87 of A992 steel is the most economical wide-flange
                               section.


                   6.7 EXAMPLE—LRFD FOR DOUBLE ANGLES
                   WITH AXIAL COMPRESSION

                               Double angles are the preferred steel shape for a diagonal in the vertical bracing part of the lat-
                               eral framing system in a multistory building (Fig. 6.2). Lateral load on the diagonal in this
                               example is due to wind only and equals 65 kips. The diagonals also support the steel beam at
                               midspan. As a result, the compressive force on each brace due to dead loads is 15 kips, and that
                               due to live loads is 10 kips. The maximum combined factored load is P u = 1.2 × 15 + 1.3 × 65 +
                               0.5 × 10 = 107.5 kips.
                                 The length of the brace is 19.85 ft, neglecting the size of the joint. A36 steel is selected because
                               slenderness is a major factor in determining the nominal capacity of the section. Selection of the size
                               of double angles is based on trial and error, which can be assisted by load tables in the AISC “Manual