Page 216 - Sustainable On-Site CHP Systems Design, Construction, and Operations
P. 216

Electrical Design Characteristics and Issues     189


             Grounding System Selection
             The following is an overview of some of the design considerations which may impact
             the grounding system selection:

                 •  Voltage. Proper generator grounding varies depending on the generator location
                    in the facility system and the voltage at which the generator will be tied to
                    the utility supply. Consider a typical situation—the utility service is medium
                    voltage, the utility transformer has a secondary voltage of 4.16 kV, and the
                    transformer has a low-impedance ground with a maximum ground fault current
                    of approximately 200 A. The facility generator is also at 4.16 kV and is paralleled
                    with the utility. In this scenario, the optimum configuration is for the CHP
                    generator neutral conductor to have a high-impedance ground, which will limit
                    the ground fault current to approximately 2 A. This fault current would be
                    sufficient to activate effectively an alarm condition while still permitting
                    continued operation until the faulted circuit is located and shutdown. In turn,
                    this avoids a total system outage.
                 •  Harmonics. Most generators manufactured today which are used in CHP systems
                    are wye-connected. Since the third harmonic components of the phase currents
                    are additive in the neutral, they can best be attenuated in the neutral. To
                    accomplish this attenuation a grounding resistor helps perform this function.
                    These grounding resistors are typically rated for a particular voltage and current
                    and are provided within a separate enclosure. When harmonics are a critical
                    issue for a facility, generator neutrals should be impedance grounded when
                    paralleled with the utility service buses.
                 •  Mode of operation. If the CHP generators are commonly not paralleled with
                    the utility source, there are other considerations which must be taken into
                    account for grounding purposes. First, if the distribution system feeds single
                    phase loads, which is typical for nonindustrial facilities, its neutral must be
                    solidly grounded so that it may be used as a circuit conductor, as required by
                    NEC 230-95. Second, if the generator is paralleled with the utility and its
                    neutral is high-impedance grounded, it cannot be used as a circuit conductor.
                    To allow for both possibilities, a common solution is to provide a bypass
                    device installed across the grounding resistor which shunts the impedance as
                    necessary.


             Bonding Requirements
             As a separately derived system, a CHP generator must be grounded and bonded as per
             NEC Section 250.30. This section of the NEC has been revised most recently in 2008 due
             to the complexity and importance of grounding and bonding these types of complex
             and interrelated electrical systems. This section gives a summary of the components of
             a well-grounded system—the system bonding jumper, the grounding electrode con-
             ductor, and the grounding electrode. For more information, consult the NEC and perhaps
             one of the many books written on this topic to further explain the grounding section
             in detail.
                Note that the summary below refers to a solidly or impedance grounded system.
             There is a separate section (250.30B) to cover ungrounded systems; however, since this
             type of grounding system is rare in CHP plants, it is not covered here.
   211   212   213   214   215   216   217   218   219   220   221