Page 293 - The Engineering Guide to LEED-New Construction Sustainable Construction for Engineers
P. 293

256    Cha pte r  S i x



                                                         Effective as per the
                                           Design        CIBSE Applications
                                                         Manual 10:2005, Fig. 2.8


                    Natural Ventilation
                                                          CIBSE Applications
                      Requirements
                                                          Manual 10: 2005 or
                                                          Manual 13: 2000 as applicable
                                         Calculations     Room-by-Room Airspace
                                          (Do Either)     Model for > 90% of
                                                          Occupied Spaces per
                                                          ASHRAE 62.1-2007, with
                                                          errata but without addenda,
                                                          Chapter 6

             FIGURE 6.2.1  Requirements for increased ventilation in naturally ventilated spaces LEED 2009.



             Mixed Mode Ventilation  LEED 2009 requires for IEQp1 that mixed mode ventilation
             meet the minimum ventilation rates in ASHRAE 62.1-2007 Section 6, regardless of the
             ventilation mode based on any acceptable engineering calculation method, although
             not specifically restated in IEQc2. LEED 2009 also has the addenda requiring that mixed
             mode ventilation follow the CIBSE  Applications Manual 13:2000, Mixed Mode
             Ventilation as listed under the natural ventilation requirements.



             Special Circumstances and Exemplary Performance (LEED 2009)
             At this time, improved indoor air quality is primarily sought by exchanging
             indoor air with air of better quality from the outside. However, this may not be
             the best solution in all cases. There are two main concerns that frequently occur.
             The first is the possibility of poor ambient air quality in some areas during different
             seasons, and the second is the increased energy use required to condition the
             additional outside airflow. Therefore, there are also other methods for improved
             indoor air quality that are being researched and recommended. Many are specific
             to a certain class of indoor air pollutants such as particulate matter or VOCs and
             may be important for some applications. These might serve as a special circumstance
             or an innovative design credit at this time, although future versions of the LEED
             rating system might add options for special cases. One of the most commonly
             used indoor air quality mechanisms is filtration, which decreases particulate
             matter, a pollutant that may carry other contaminants such as microbes or
             allergens. Improved filtration is partially addressed in the IEQ credit subcategories
             3 and 5. Some other methods are mentioned in the Discussion and Overview
             section of this chapter.
                 There is no EP point associated with IEQ credit 2 in either the 2.2 or the 2009 version
             of LEED.
   288   289   290   291   292   293   294   295   296   297   298