Page 326 - The Engineering Guide to LEED-New Construction Sustainable Construction for Engineers
P. 326

288    Cha pte r  S i x





























             FIGURE 6.8.2  Natural lighting at Cox and Dinkins, Engineers and Surveyors, Columbia, S.C.
             (Photograph taken June 2007.)


                 IEQc8.1 has also been listed as available for an EP credit in LEED-NC 2.2 and LEED
             2009. This additional point can be achieved if at least 95 percent of the regularly occupied
             spaces are daylighted by the minimum glazing factor as in LEED 2.2 Option 1, the
             prescriptive option in LEED 2009 or the minimum 25 fc as simulated or measured for
             either version. This corresponds to the following requirement:
                                DC ≥ 95    additional EP point criterion         (6.8.5)

             Since Option 3 in either version is based on measurements that can only be taken on
             two days of the year, and under restrictive weather conditions, it may cause a scheduling
             conflict for certification if the weather is not favorable. In that case, a description of
             special circumstances regarding the measurements taken on alternate dates may need
             to be included in the submittals.
             IEQ Credit 8.2: Daylight and Views—Views (for 90% of Spaces)
             IEQc8.2 is worth one point in both LEED 2.2 and LEED 2009
             USGBC Rating System
             LEED-NC 2.2 lists the Intent, Requirements, and Potential Technologies and Strategies
             for IEQc8.2 as follows and is essentially identical for LEED 2009:

                Intent
                Provide for the building occupants a connection between indoor spaces and the outdoors through
                the introduction of daylight and views into the regularly occupied areas of the building.
                Requirements
                Achieve direct line of sight to the outdoor environment via vision glazing between 2 feet
                6 inches and 7 feet 6 inches above finish floor for building occupants in 90% of all regularly