Harmonic Distortion of the Supply
            122   Chapter Four




















































            Figure 4.2 Circuit diagram, operating sequence, and idealized currents of a three-phase
            bridge rectifier.


              It follows that a three-phase bridge will take harmonic currents of
            the orders 5 and 7, 11 and 13, 17 and 19, etc. and if the pulse number
            is increased to 12 by adding a second bridge with a phase displacement
            of 30°, harmonic currents of the orders 5 and 7, 17 and 19, etc., will be
            suppressed leaving only the orders 11 and 13, 23 and 25, etc. The
            Fourier analysis indicates that the magnitudes of these harmonic cur-
            rents are similarly based on a simple mathematical relationship.