Page 7 - Uninterruptible Power Supplies
P. 7

Standby Power Generating Sets
                                                Standby Power Generating Sets  5


            base load type of operation is not envisaged. Some installations may be
            required to continue running for long periods  after  normal  supplies
            have failed (e.g., some military installations) and in such cases 1000-rpm
            engines should be considered above approximately 1 MW. Most diesel
            engines in use are of four-stroke type, but two-stroke engines may occa-
            sionally be encountered. Diesel engines are designed to run on Class A
            fuel to BS2869 which has a calorific value of about 42.7 MJ/kg; before
            running on any other fuel, advice should be obtained from the engine
            manufacturer. The efficiency of a modern turbocharged engine may be
            about 40 percent but this does not take into account any auxiliary drives
            or the generator losses; the overall efficiency of the generating set will
            be less.
              The useful energy produced by the engine passes through the cou-
            pling to the generator but, depending on the arrangement of the set, it
            is not always possible to use all the energy to supply the intended load.
            Sets up to a few hundred kVA are usually self-contained but larger sets
            may require power for auxiliary items such as cooling and ventilation
            fans. The requirement will be small, only a few percent of the genera-
            tor rating. There may also be incidental extras such as engine room
            lighting and small power and fuel pumps.
              A naturally aspirated diesel engine is capable of accepting full load
            in a single step but, in order to reduce the size and cost, many modern
            engines are turbocharged. This reduces the step load capability and a
            modern turbocharged engine with a high brake mean effective pres-
            sure (see below) will probably accept only 60 or 70 percent of its rated
            load in one step. It follows that for most installations a load switching
            sequence has to be followed after the starting procedure.
              With a naturally aspirated engine the quantity of combustion air
            within the combustion space is constant and there is always sufficient
            oxygen for combustion of the maximum amount of fuel. With a tur-
            bocharged engine the quantity of surplus combustion air available at
            any one time is limited by the turbocharger. A step load change may
            cause a sudden increase in the amount of fuel injected but there will be
            inadequate combustion air until the turbocharger has had time to
            accelerate.
              Generating set manufacturers recognize four categories of load accep-
            tance and categories 1, 2, and 3 are typical of the sets used for standby
            generation:

              Category 1   100 percent
              Category 2    80 percent
              Category 3    60 percent
              Category 4    25 percent



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   2   3   4   5   6   7   8   9   10   11   12