150                 Valve  Selection Handbook

              However,  the  speed  with which  forward  flow  retards  can  vary greatly
            between  fluid  systems.  If,  for  example,  the  fluid  system  incorporates  a
            number  of  pumps  in  parallel  and  one  fails  suddenly,  the  check  valve  at
            the outlet  of  the pump that failed  must close  almost  instantaneously.  On
            the other hand, if the fluid system  contains  only one pump that  suddenly
            fails,  and if the delivery  line is long  and the back  pressure  at the outlet of
            the  pipe  and  the pumping  elevation ^re  low,  a  check  valve  with a  slow
            closing characteristic  is  satisfactory.

























            Figure 4-13. Diaphragm  Check Valve with Ring-Shaped Pleated Diaphragm.
            (Courtesy of  VAG-Armaturen  GmbH.)





















            Figure 4-14. Diaphragm Check Valve, Incorporating  Flattened Rubber Sleeve
            Closure Member.  (Courtesy of  Red Valve Company Inc.)