Table A-2.4  Section VIII  Requirements

 PRESSURE RELIEF DEVICE OPERATING  REQUIREMENTS
 ALLOWABLE VESSEL
 OVERPRESSURE  SET PRESSURE TOLERANCE
 (ABOVE MAWP OR VESSEL  SPECIFIED  WITH RESPECT TO SET  REQUIRED
 APPLICATION  DESIGN PRESSURE)  PRESSURE SETTINGS  PRESSURE  BLOWDOWN
 SECTION VIII  Div. 1 & 2
 All vessels unless an exception  10% or 3 psi - whichever is greater  < MAWP of vessel  ±2 psi up to and including 70 psi  None  specified
 specified  (UG-125C)  (AR-150a)  (UG-134a)  (Afl-141)
         ±3% over 70 psi
 Exceptions:  16% or 4 psi - whichever is greater  One valve < MAWP, additional  (UG-134 d1) (AR-120d)
 When multiple devices are used  (UG-125C1)  (AR-150b)  valves up to 105% of MAWP
 (UG-134a)  (AR-142a)
 Supplemental device to protect  21%(UG-125c2) (AR-150C)  Up to 110% MAWP  Note:
 against hazard due to fire  (UG-134b)  (AR-142b)  Pressure relief valves for
                           compressible fluids having an
 Device to protect liquified  20% (UG-125c3a)  <MAWP(UG-125c3b)  -0%  +10%  adjustable blowdown construction
 compressed gas storage vessel in  (UG-134d2)  must be adjusted prior to initial
 fire (Div. 1 only)        capacity certification testing so
                           that blowdown does not exceed
 Bursting disc  Same as above  Stamped burst pressure to meet  ±2 psi up to and including 40 psi  5% of set pressure or 3 psi,
 requirements noted above  whichever is greater
 (UG-134 - Note 56) (AR-140 -  ±5% of stamped burst pressure at  (UG-131 c3a) (AR-512)
 Note 15)  specified coincident disk
         temperature  (UG-127a1a)
         (AR-131.1)
                                    1 psi = 6.89 kPa
 Table A-2.5  Section X  Requirements

 PRESSURE RELIEF DEVICE OPERATING RE(QUIREMENTS
 ALLOWABLE VESSEL
 OVERPRESSURE  SET PRESSURE TOLERANCE
 (ABOVE MAWP OR VESSEL  SPECIFIED  WITH RESPECT TO SET  REQUIRED
 APPLICATION  DESIGN PRESSURE)  PRESSURE SETTINGS  PRESSURE  BLOWDOWN
 SECTION X
 All vessels unless  exception  10% or 3 psi - whichever is greater  < Design pressure  Ref. Section VIII  None specified
 specified  (RR-130a)  (RR-120)  (RR-111)
 Exceptions  16% or 4 psi - whichever is greater  One valve < design pressure.
 When multiple devices are used  (RR-130b)  Others up to 105% of design
 pressure
 Additional hazard due to fire  121%
 (RR-130C)
                                   1 psi = 6.89 kPa