Page 115 - Battery Reference Book
P. 115

Recombining sealed lead-acid batteries  3/6
       Hawker Energy Ltd Cyclon range of  sound electrode   Table 3.1  Characteristics of  standard cells
       combination  batteries  and  the  Hawker  Energy  Inc.
       range  discussed  above  are  equivalent  and  hence  the    D        X       BC
       Chloride  product,  available  in  the  UK,  will  not  be   Nominal voltage (v)
       discussed in great detail here.                              2.0      2.0     2.0
         These batteries are contined in a polypropylene case   Capacity rating (Ah)
       with a metal outer canister and are available as single   10 h rate   2.5   5.0   25
       cells and in battery packs including a lantern battery.      (250mA)  (500mA)   (2.5 A)
       Batteries  will be  specially designed and produced  to   1 h rate   2.8   3.2   20
                                                                             (5A)
                                                                    (2.5A)
       meet customers'  requirements.              Peak power rating (W)  135   200   (25 AI
                                                                                     600
         The standard types of  cell now available are the D,       (at 135 A)  (at 200A)  (at 600A)
       X and BC cells (Table 3.1).                 Internal resistance
         Temperature ranges are -65  to +65T (storage and           10       6
       discharge) and  -40  to +65"C  (charge). Storage lives   (x10-3~)             2.2
       from full charge are  18 years at o"C, 3 years at 25°C   Diameter (mm)   34.2   44.4   65.7
       and 1 year at WC. The expected cycle life varies from   Height (mm)   67.6   80.6   176.5
       300 to  2000  cycles  and the  float life is  8-10  years.   Weight (kg)   0.181   0.369   1.67
       Charging is by  most conventional methods  including
       constant  voltage,  constant  current,  taper  charging,
       pulse  charging,  etc.,  according  to  the  application.   Batteries (6 and  12V) are available with capacities
       Self-discharge is typically  6-8%  per  month  at room   in the range 2.7-52A  (20h rate), 2.5-50A  (10h rate).
       temperature.                                  The characteristics (including discharge characteris-
         The  manufacturers  claig that  the  D  cell  will  give   tics, battery life, safety, storage and battery testing) of
       instantaneous discharges of up to 100 A and sustained   sealed lead-acid  batteries have been discussed further
       discharges of  up to 30A. Double these figures can be   in  a  book  published  by  Gates  Energy  Products  (see
       obtained  with  the  X  cell,  and  up  to  800A with  the   Bibliography).
       BC cell.
   110   111   112   113   114   115   116   117   118   119   120