Nickel-cadmium secondary batteries 51/47
0 10 20 30 40 50 60 70 80 90 100
la) Type H Capacity 1%)
Capacity (%)
lbi TypeM
- 1.3
-
aJ
u 1.2
-
>
.-
g 1.1
m
-
g 1.0
0)
g 0.9
L
0.8
0
0.7
0 10 20 30 40 50 60 70 80 90 100
Capacity (%I
IC/ Type L
Figure 51.32 Typical discharge characteristics at 25°C for Nife large vented nickel-cadmium batteries (Courtesy of Nife Jungner)
Table 51.52 Electrical performance data for McGraw Edison low-rate vented nickel-cadmium batteries, CED series
Cell type Discharge current (A) to 1.14V at 25°C
Nominal 10h 8h 5h 4h 3h 2h Iih lh
c,apacity
(Ah)
CED-16 16 1.53 1.87 2.83 3.34 3.97 4.9 5.4 6.25
CED-32 32 3.07 3.74 5.7 6.5 7.7 9.4 10.6 12.3
CED-43 43 4.12 5.01 7.65 8.6 10.2 12.1 13.7 15.8
CED-58 58 5.5 6.75 9.1 10.2 11.45 13.25 14.5 16.6
CED-79 79 7.58 9.31 13.1 14.6 16.7 19.6 22 25
CED- 100 100 9.6 11.8 16.9 18.8 22 26.1 29.2 33
CED-120 120 11.5 14.1 19.4 22.2 26.1 31.1 34.3 39.1
CED-150 150 14.5 17.7 24.1 27.6 32.2 38.9 42.7 48.8
CED- 183 183 17.5 21.6 30 34 39.7 47.9 52.7 59.5
CED-216 216 20.8 25.5 36.2 41 47.6 57.1 63.1 72
CED-250 250 23.8 29.4 41.4 47.6 56.1 67.1 73 83