Page 50 - Boiler Operator’s Handbook
P. 50

Operating Wisely                                                                                     35


               Just the same, you should be able to do it. Read the  minal 4 in the panel. To quickly isolate a problem start
               drawings and sequence of operation until you under-  testing at the middle of the circuit, and terminal 4 is in
               stand how your system works then review it every year  the middle in this example. If the light works then the
               so you will have most of it in your head when the need  break or open is closer to the grounded conductor and
               to solve a problem comes up.                         you can forget checking everything before terminal four.
                    What good was that test lead? Well, all you had  If the light doesn’t work then the break or open has to
               to do was touch the end of it to one of the terminals or  be between the hot lead and terminal four. Once you’ve
               wires in the system (while holding the insulation on the  figured out which side contains the open you can test at
               wire so you don’t light up) and see if the test light comes  a point near the middle of the part of the circuit that you
               on. If the light comes on then there’s a closed circuit  just isolated. You should pick terminal 3 or 5 depending
               up to that point. If it’s not on then you know there’s an  on which end of the circuit must have the break because
               open somewhere between the power supply and that  they’re conveniently in the panel. If the light didn’t
               terminal. When one terminal is hot and the next one isn’t  work at 4 or 3 then check the wire connected at the on/
               you can look on the drawing to see what’s connected  off  switch  because  it’s  also  conveniently  in  the  panel.
               between the two. If it’s supposed to have a closed con-  You’ve isolated a problem when you find the spot where
               tact at the stage you’re looking at then you go out into  the light doesn’t work when checking after a device and
               the  plant  to  find  the  device  to  see  what’s  wrong  with  does before it. Of course that doesn’t mean that there
               it. The device could be broken or it could be valved off   isn’t a problem with something else in the circuit that’s
               (although there aren’t supposed to be valves between  between the problem you found and the left connection
               a boiler or burner and the limit switches). It could be  of the FMS. It’s slightly more complicated because other
               something as dumb as a screw vibrated out and the  parts  of  a  circuit  must  be  activated  first  but  once  you
               switch  flopped  over,  something  that  really  screws  up  determine where the circuit is open it’s a lead to finding
               mercury switches.                                    out what’s preventing operation.
                    Figure 1-10 is an example of a circuit test. For some     If  a  fuel  safety  shut-off  valve  should  open,  but
               reason the fan motor starter (FMS) coil isn’t energiz-  doesn’t, you can check its terminal (when the burner
               ing to start the fan. The test light is connected to the  management system indicates it should be energized)
               grounded conductor. That upside down Christmas tree  to see if it’s getting power (light on). If it isn’t then you
               symbol is normally used to represent a ground wire  can check back through the panel circuitry to find what’s
               connection. The clip on my test light allows me to slip  open.  Keep  in  mind  that  you  only  have  ten  or  fifteen
               it over any grounded metal part of the boiler plant for  seconds to do that most of the time and you’ll have to go
               testing but there’s times when something accessible  through several burner cycles until you spot the prob-
               and metal isn’t grounded even if it should be so don’t  lem. If the output terminal is energized then you’ll have
               count on it. The other side of the light is connected to a  to check the power at the valve to be certain it’s not a
               test lead with an insulated handle and extended metal  loose or broken wire between panel and valve motor.
               probe. Mine was recovered from a broken meter that       I used to take it for granted but got stung so many
               someone threw away. Always check your test light by  times that now I always check to be certain a burner
               tapping a hot lead to ensure it’s working before testing.  management  system is properly  grounded.  Lack  of
               You’ll note the test lead is indicated to be touching ter-  a ground can produce some very unusual and weird
                                                                    conditions. Anytime you see lights that are about half
                                                                           bright or equipment running that’s noisy and
                                                                           just not normal look for lack of a ground or an
                                                                           additional one.
                                                                                Exactly what is a ground? It’s anything
                                                                           that  is  connected to  a  closed  circuit to mother
                                                                           earth. In most plants there is a ground grid, an
                                                                           arrangement of wires laid out in a grid under-
                                                                           ground and all interconnected to each other and
                                                                           the steel of the building to produce a ground-
                                                                           ed circuit. At your house it’s your water line
                                                                           and possibly also separate copper rods driven
                           Figure 1-10. Testing a control circuit          straight into the ground. A ground wire is any
   45   46   47   48   49   50   51   52   53   54   55