Page 112 - Boiler_Operators_Handbook,_Second_Edition
P. 112

Boiler Plant Operations                                                                              97


               around a boiler plant there will be significant deteriora-  ravages of weather, etc., simply because the plant had no
               tion of the boiler’s interior unless protected. To prevent  need of it. Later, when they attempted to sell it, the con-
               corrosion the boiler should be free of moisture. After the  dition was so bad they couldn’t and their only option for
               boiler is drained all drain valves should be closed, the  removing it was to pay for its removal. Even if you don’t
               drum covers or inspection openings opened and dry  need the equipment, preserve it. Someone may need it
               air blown through the boiler to remove any remaining  and, if it’s in good shape, the owner will get enough for
               moisture. Checking the exhaust air with a hygrometer  it to pay for its removal. Otherwise you may be looking
               until the humidity in the boiler is less than 10% or 5%  at that rusting hulk until the day you retire.
               above the humidity of the drying air is recommended.     When the whole plant is put in lay-up these guide-
               Then, insert a package of silica gel with a corrosion  lines can be extended to other equipment. Special
               proof drain pan under it and close the boiler completely.  consideration should be given to a long-term lay-up.
               The air will simply compress and expand in the boiler  Valves and Pumps with packing should have the pack-
               as it heats and cools so there is no reason to install an  ing removed and replaced with fresh material heavy
               expansion tank. The silica gel must be checked twice  in graphite. Packing that was in use and allowed to
               a year to ensure it is active. Any moisture found in the  dry will harden and be almost impossible to remove
               drain pan should be removed.                         later. Pumps that have mechanical seals can’t be reli-
                    The fire sides of the boiler have to be considered  ably preserved but you could try disassembling the
               for long-term lay-up. The connection to the stack and  seals, coating the sealing surfaces with a mineral oil
               the  combustion  air  inlets  should  be  blocked  off.  The  and reassembling them. Pumps containing oil and such
               enclosed spaces should be dried and maintained with a  materials that lubricate without freezing can simply be
               silica gel dryer as described above.                 isolated after filling with liquid that is confirmed water
                    Normally boiler control panels, motor starters,  free and not prone to form acids while stagnant. Pumps
               etc. can be maintained by simply leaving the power on  containing water should be drained completely, close
               the panels. The indicating lights in the panels should  their supply and discharge valves, then use the vent and
               supply sufficient heat to lower the internal humidity  drain connections to blow dry air through them and dry
               and prevent corrosion from moisture. If the panels are  them completely before isolating.
               exposed to the weather addition of some light bulbs in-
               side to lower the humidity is recommended. Wiring two
               100 watt lights in series will produce about 25 watts of  TUNE-UPS
               heat but the likelihood of one of the bulbs failing is very
               low. Add lights to panels that do not have any. Motors     While I prefer the title “tune-up” the PhD’s at the
               for combustion air fans, boiler water feed or circulating  EPA who like to use longer words have chosen to use
               pumps can be heated by applying reduced voltage to the  the title “Combustion Optimization” for the same thing.
               windings or using heaters that are supplied for such a  This edition is revised to include a section for Combus-
               purpose.                                             tion Optimization in the Chapter on maintenance be-
                    Always refer to the manufacturer’s instruction  cause it’s a normal maintenance function. It’s included
               manuals for suggestions or requirements for lay-up. Re-  in the startup of a new boiler and operation of the plant
               gardless of how the boiler is laid up its condition must  during a tune-up is covered here.
               be monitored on a regular basis, preferably weekly, to     Along the east coast of the US I’ve found that
               ensure it is not deteriorating. All you’re normally doing  it’s uncommon for a boiler operator to be expected to
               is making sure the seals are intact (nobody opened it and  perform the tune-up of a boiler. A few plants do their
               left it) and there’s no external signs of corrosion or other  own tune-ups but use other personnel with labels like
               problems. Initially test water during wet lay-up on a  Instrument Technician to do the work. Rarely is it done
               weekly basis to ensure it has sufficient sulfite to remove  by a licensed boiler operator. Tune-ups should be per-
               any oxygen. When testing reveals consistent retention of  formed on an annual basis and whenever there’s reason
               the sulfite extend the testing interval until a period with  to believe the controls are out of tune and it is always
               a drop of 10 ppm is experienced and incorporate that  the boiler operator’s role to identify a problem with the
               testing interval in your SOPs. Check silica gel inside the  controls that require a tune-up.
               furnace on a monthly basis and inside the boiler on a     Another factor in tune-ups are the requirements of
               semi-annual basis.                                   the local environmental office, whoever is responsible
                    All too often I’ve seen a boiler abandoned to the  for enforcing the Clean Air Act. Many states now require
   107   108   109   110   111   112   113   114   115   116   117