118                                                                               Boiler Operator’s Handbook

               three times as much energy in fuel as it delivers to the  ated by the gallons of oil or therms of gas burned to get
               facility. Now consider the fact that so many boilers are  it. Don’t, as one plant in Missouri did, simply put 122
               outsized so they’re running at those low loads most of the  in the column on the log for evaporation rate because
               time and that cycling efficiency becomes meaningful.  that’s what it is. In that instance, and in many others, I
                    Uh oh! Used another word that isn’t in the diction-  found the operators put a value in the log that the chief
               ary. Outsized means the boiler is no longer the right  wanted so everyone was happy. It wasn’t anywhere
               size for the facility. With added insulation, sealing up  near the actual value which could be calculated from the
               air leaks, adding double glazing, and other activities to  other entries in the log.
               conserve energy we have decreased the load so much       In the case of the Missouri plant I upset everyone
               that the boiler is now too big for it. It got outsized! I can’t  because I did the math and showed the actual value was
               guarantee that it wasn’t too big to begin with because  around 108 pounds of steam per gallon of oil and that
               that’s usually a fact, but calling it outsized doesn’t raise  two of the three operators managed to run the plant so
               the hackles of engineers like telling them they oversized  their value was 105 while one managed to maintain 114.
               it does.                                             Once the other two were clued in as to what they were
                    When a modulating heating boiler is cycling at  doing wrong, and settled down, the average went to 114.
               temperatures that are halfway between the winter  There were sound reasons why the plant couldn’t man-
               design low and 65°F cycling efficiency has to be deter-  age an evaporation rate of 122 but, since the manager
               mined because it’s so low that replacing that boiler with  wouldn’t accept anything less, the operators put what
               one that’s the right size (perhaps you’ve heard of right-  he wanted in the log book.
               sizing, it’s been the rage) fuel savings will pay for it in     Evaporation rate can be used to compare boilers
               one or two heating seasons. Use that half the load and  to each other and to performance at other loads and at
               cycling determination to identify boilers that are cycling  other times. It’s comparable to a boiler efficiency as far
               excessively and get an engineer to do an evaluation to  as variations is concerned. A change in evaporation rate
               determine if the boiler should be replaced.          should be relative to a change in combustion efficiency.
                    Perhaps the boss won’t go to the expense of hir-     Of course that doesn’t come close to monitoring
               ing an engineering firm to do it but you might suggest  plant efficiency. For that you have to compare the de-
               he contact an ESCO (Energy Service Company) and  livery rate, how many pounds of steam you deliver to
               invite them to look into it. ESCO’s install modifications  the facility divided by the amount of fuel burned in the
               to plants to reduce energy consumption and get their  same time frame.
               money back from the savings with no money layout by      The actual value of the number itself isn’t im-
               the owner.                                           portant. The object of calculating these rates is to see if
                                                                    they’ve changed and, if so, did they change for the better.
                                                                    Whatever you use it should be treated as a flexible num-
               PERFORMANCE MONITORING                               ber with a goal of increasing or decreasing it depending
                                                                    on how you calculate it. The concept is exactly the same
                    Calculating boiler efficiency may not be consid-  as monitoring your gas mileage on your car where the
               ered part of the duties of a boiler operator. Monitoring  miles per gallon dropping off indicates there’s something
               and optimizing plant performance is. To make it simple  wrong or you just did a lot of city driving you normally
               we use values that are less complicated to determine,  don’t do. Changes in the rate can be an indication of im-
               and easier to understand and work with. Of course you  proved performance or changes in the load.
               have to understand how they’re calculated, and whether     Evaporation rate provides a value very consistent
               you want the results to be higher or lower to indicate an  with boiler operating efficiency and delivery rate is con-
               improvement in performance or they’re a waste of time.  sistent with plant efficiency so they are good parameters
                    If you want to work in terms of efficiency the pre-  to measure, log, and compare to monitor your perfor-
               vious section provides guidelines to do just that. Don’t  mance and the performance of the plant.
               be surprised if you get numbers that seem out of place     Evaporation rate can indicate problems that can’t be
               but don’t accept them as true either. It’s simply unrealis-  determined by combustion analysis or other methods of
               tic to believe something can operate at more than 100%  monitoring boiler efficiency because the latter are instan-
               efficiency, even if the calculations are accurate.   taneous readings. Frequently combustion analysis are
                    The best method for evaluating steam boilers is  performed while the boiler controls are in manual and the
               evaporation rate. Divide the quantity of steam gener-  service technician has adjusted them to optimum. That