Page 128 - Boiler_Operators_Handbook,_Second_Edition
P. 128

What the Wise Operator Knows                                                                        113

                    You shouldn’t confuse matching loads and react-  EFFICIENCY
               ing to changing loads however. I was in one plant that
               started up a boiler every morning to handle the warm-     There are so many definitions of efficiency and
               up as the night set-back thermostats switched back up.  many operators (and most engineers) are confused as to
               An hour or two later the boiler was shut down until the  which is which or simply assume they are all the same.
               next morning. First of all, that’s rough on the boiler and  I shall attempt to define the many different labels of ef-
               it’s really shortening its life. It’s also wasting a certain  ficiency and to clarify what they actually represent. I’ve
               amount of energy because what it took to heat the boiler  even created a couple of definitions because I’m certain
               up is lost up the stack before the next morning. If an  there’s a need for them.
               operator is doing his job of checking all the operating     The  first  point  of  confusion  involves  the  defini-
               limits when a boiler is started then that daily start-up  tion of boiler efficiency. It can be officially defined as
               would be rough on the operator; most don’t seem to  one hundred times the heat absorbed in the steam and
               bother.                                              water divided by the heat energy added by the fuel and
                    Short-term operation for an intermittent peak load  other sources of energy. That’s the definition established
               shouldn’t be considered unless there are problems with  by the ABMA and the one most of us accept as the true
               the steam pressure or supply water temperature drop  definition. Those other sources of energy include electric
               associated with that load. In other words, it’s okay for  power supplied to the fans, and pumps that are integral
               the steam pressure or water temperature to drop a little  to the boiler. If all of those values we engineers call “in-
               when everything starts heating up in the morning. The  puts” are accounted for then we get a correct value of
               drop will limit the heat flow to the load because there’s  efficiency. However, it’s the one that is seldom used.
               a smaller temperature difference and everything will     The energy added to the water and steam is the
               eventually recover. Don’t hesitate to try it. Let the pres-  “output” of the boiler. There can be multiple outputs
               sure or temperature drop. A slight dip in conditions on  that have to be considered. If the boiler has a reheater
               an operating boiler is much less damaging than running  the energy added to the steam that flows through the
               a boiler up from cold.                               reheater is an output in addition to the water that is
                    If the pressure or temperature dips can’t be toler-  evaporated to produce steam and the energy added in
               ated you’ll learn quickly what average night-time tem-  the superheater.
               perature signals that limit so you can have more boiler     Note that the official definition of boiler efficiency
               capacity in operation when it’s necessary.           considers output to include all the heat absorbed by the
                    I  also  want  to  mention  those  plants  where  no-  water and steam. That includes the heat added to the
               body seems to notice or care what the boiler to load  water that’s lost in blowoff and blowdown but not the
               relationship is. It’s not at all uncommon for me to find  heat lost in steam for sootblowing. Since the boiler’s
               a two boiler hot water plant where both boilers are  output that we get to use doesn’t come from blowoff
               always operating. In most of those plants the boilers  or blowdown water or sootblowing steam how can it
               were each sized to carry the full load and the operators  be counted as output? It’s counted because the boiler
               discovered they could shut one down and never worry  manufacturer has no control over the quality of water
               about having enough boiler capacity. The cost of fuel  used to make steam and no control over the fuel fired
               to simply keep a boiler hot can be considerable so they  and how cleanly it’s fired. The boiler manufacturer is
               also found that they saved the owner a lot of money.  concerned with the heat that’s transferred through the
               Of course you have to shut at least one valve when you  tubes.
               shut down that hot water boiler. Otherwise the hot wa-     Soot blower operation to maintain boiler condi-
               ter flowing through it will heat up a lot of air that’s lost  tions is one of the reasons that a boiler efficiency test
               up the stack.                                        in accordance with ASME PTC-4.1 (Steam Generating
                    Don’t think you have to run a proportion of boil-  Units Power Test Code) is supposed to be run for a mini-
               ers to match the load. I’ve been in many plants with  mum of twelve hours. The Test Code does account for
               four boilers, any one of which could carry the full load  the sootblower steam because it’s required to keep the
               of the facility served. They’ll run one or two boilers in  heat transfer surfaces clean.
               the summer and three in the winter whether they need     Several years ago the ABMA (American Boiler
               them or not. They’re also usually the plants where the  Manufacturer’s Association) agreed to guanantee ef-
               boilers are regularly switched so they will all wear out  ficiency at only one firing rate and, unless otherwise
               at the same time.                                    specified by the customer, set it at full load. If you have