Page 123 - Boiler_Operators_Handbook,_Second_Edition
P. 123

108                                                                               Boiler Operator’s Handbook

               thermostats are reset in the morning. When it’s very cold  how many people are in the building or a certain area of
               out the temperature of walls and other surfaces exposed  the building. The new technical name for that is demand
               to the outdoors will drop quickly and may be cooler  controlled ventilation. If you don’t have the advantage
               than the 55°F. Because partitions, floors and ceilings,  of  one  of  those  specialized controls you’ll probably
               furniture, etc. cooled slower, they might still be warmer  have systems like time clocks that set the ventilation at
               and help offset the effect of the colder walls. Warm-up  a minimum when people aren’t supposed to be in the
               loads can be higher than heating loads if ventilation is  building and adjust them to a value for full occupancy
               not controlled. Unless the thermostat settings are timed  the rest of the time.
               to compensate for the variation in storage temperatures     Any of those controls should be set for minimum
               you may get some complaints in cold weather or waste  ventilation air during the period when the building is
               heat in milder weather.                              warming up in preparation for occupancy. That way
                    Ventilation loads are primarily people loads. For  you avoid the ventilation load while handling the warm
               all practical purposes a facility has to introduce 20 cfm  up load to limit the load on your boilers. It also makes
               (cubic feet per minute) of fresh outside air for every per-  no sense to heat up cold outside air to warm up walls.
               son in the facility. There are more specific requirements  The ventilation should increase for a short period before
               that vary with the Jurisdiction but that is a good rule of  people start entering the building to flush out the stale air.
               thumb. Many older facilities may still be set for ventila-     Except for some process requirements the hot wa-
               tion rates as low as 5 cfm per person so it pays to check  ter heating load is largely a function of people activities.
               the actual values before trying to determine the heating  People have a direct relationship with hot water needs
               load they create. The amount of heat required for ventila-  for cooking, showers, and washing. Each of those hot
               tion air is easy to determine, it’s the total of ventilation air  water uses is sporadic, occurring at specific (sometimes
               in cfm multiplied by a constant of 1.08 and the difference  inconsistent) times so they’re more on and off than a
               between the outdoor air temperature and room tempera-  constant load. There are several means of producing
               ture. As an example, for 100 people you need 2,000 cfm of  hot water and satisfying the irregular loads so there’s
               0°F outside air which requires 162,000 Btuh (2,000 × 1.08 ×  a section in this book devoted specifically to hot water
               (75 – 0). If you recall our earlier discussion that’s equiva-  heating. When the hot water is heated by many heat ex-
               lent to about 162 pounds per hour of steam. Note that we  changers throughout the facility you have little control
               used 75° not 65° because we can’t count on the heat from  of those loads and you’ll have to monitor plant loads to
               people, etc. to cover that portion of the load.      determine their effect.
                    In areas containing a high concentration of people     An unusual load that I encountered at one chemi-
               (movie theaters, stadiums, office buildings) the ventila-  cal production facility a few years ago is a rain load. I
               tion load can be the largest single load of the facility. The  was collecting nameplate data at one of the boilers and
               core of a building, in the middle where there are no out-  found myself almost run over by the operator who was
               side walls, and floors and ceilings separate them from  suddenly rushing around trying to get that boiler operat-
               other occupied spaces, the ventilation air can produce  ing. Once he had it on line I asked what the rush was all
               a heating load that would not exist without it. If your  about. “It’s about to rain” was his simple reply. That plant
               facility has large changes in the number of people from  experienced a 30,000 pph increase in boiler load every
               day to night or over weekends you should see swings in  time it rained! Many district heating plants experience
               load due to changes in the ventilation air.          a delayed rain load which is due to rain leaking into the
                    Of course many older buildings don’t adjust venti-  manholes and tunnels containing the steam lines. It’s a
               lation air depending on building occupancy. Yours may  load that indicates inadequate or ineffective maintenance
               be one that continues full flow ventilation at night when  and shouldn’t be as significant as that one plant. You may
               There are only a few people, if any, in the building. If  have one and it shouldn’t be difficult to identify it.
               you have a way of closing that off at night (you’ll never     Finally, there are production loads. These are
               be able to get zero ventilation) you’ll save a lot on heat-  requirements for heat to warm raw materials for pro-
               ing all that air unnecessarily.                      duction, to convert the product to another form (like
                    Modern facilities are using a combination of se-  melting it) or steam actually injected into the product to
               curity and air conditioning controls to determine how  alter it. They can include tank heating and heat tracing
               many people are in the building and adjusting ventila-  where heat is used to keep the product in tanks and pip-
               tion loads accordingly. Another method is measuring  ing hot enough that it will flow or remain a liquid. Those
               the carbon dioxide content of return air which indicates  heating requirements are independent of actual produc-
   118   119   120   121   122   123   124   125   126   127   128