Page 143 - Boiler_Operators_Handbook,_Second_Edition
P. 143

128                                                                               Boiler Operator’s Handbook

                                                                    delay in response to changes in the boiler firing rates.
                                                                        Checking the temperatures and a little math will
                                                                    allow you to determine what percentage of the water is
                                                                    flowing through the operating boiler. When waters of
                                                                    two different temperatures are mixed the resulting tem-
                                                                    perature is dependent on the quantities of water at each
                                                                    temperature. The percentage of water flowing through
                                                                    a  boiler  will  equal  the  difference  between  the  mixed
                                                                    water  temperature (Tm)  and the return temperature
                                                                    (Tr) divided by the difference between the boiler outlet
                                                                    temperature (Tb) and the return temperature times 100;
                                                                    boiler water flow as % of total = (Tm-Tr) ÷ (Tb-Tr). This
                                                                    formula comes in handy when you want to know how
                                                                    much water is in each part of a mixture.
                                                                        You can also use the basic formula for energy to
                                                                    determine how much heat is lost in an idle boiler, the
                                                                    temperature at the outlet will be lower than the temper-
                                                                    ature at the inlet. As in all cases where you’re comparing
                       Figure 4-5. Hydronic boilers in series
                                                                    differences in gauge or thermometer readings it’s a good
                                                                    idea, where possible, to switch the devices so you have a
               of arrangement put a cardboard blank over the com-   different reading from the same instrument.
               bustion air inlet to minimize the airflow due to draft.     Series operation of hydronic plants requires the
               The hot boiler will still waste heat to the boiler room as  piping arrangement allow for total flow through each
               radiant losses and some thermosyphoning of the air will  boiler and means for isolating the boiler which requires
               occur in the stack so it’s not the best solution.    three valves, two valves to isolate the boilers and one for
                    Closing one of the valves (supply or return) on  bypass as shown in Figure 4-5. The water is heated first
               an idle boiler will eliminate the heat losses but it will  in one boiler then its temperature is raised further in the
               change system and boiler flows and those effects have  second boiler. These systems commonly use a header
               to be considered. Some boiler plants have a bypass line  temperature controller to regulate the firing rate so the
               between the supply and return headers that simulates  two boilers fire at the same rate. When the boilers are
               the pressure drop of one boiler so you can open it after  controlled independently the modulating controller for
               closing off a boiler to restore the flow rates in the operat-  the first boiler has to be set lower than the second one so
               ing boiler and system to normal.                     it doesn’t take all the load.
                    When operating with less than the full comple-      Without the common controller you will find your-
               ment of boilers on line and bypassing around or through  self constantly adjusting the controller set points (or
               others be aware that the system supply temperature will  firing one boiler on hand) to fire the two boilers evenly.
               be less than the boiler outlet temperature because it is  An alternative to the common controls is using the po-
               mixed with the return water flowing through the idle  sition of the second boiler as a controller for the firing
               boilers or bypass. Some plants use a header temperature  rate of the first boiler, simply adding another rheostat
               control so the idle boilers or bypasses doesn’t change  to the modulating motor of the first boiler and installing
               the hot water supply temperature. It will require higher  a selector switch will allow both single and two boiler
               temperatures in the operating boiler.                operation.
                    If you have a common header temperature control
               it should be on the return. These systems usually have a
               proportional control so the firing rate of the boiler will be  BOILER WATER CIRCULATING PUMPS
               proportional to the difference between return tempera-
               ture and the set point (desired return temperature). The     Boiler water circulating pumps are common on hot
               return temperature will be held near the set point but the  water heating boilers and consist of a small pump that
               supply water temperature will vary depending on the  delivers a fraction of the total flow through the boiler. The
               blend of firing and idle boilers or bypasses. It won’t hold  purpose of the pump is to help eliminate thermal shock.
               a constant return temperature either because there’s a  They pump enough water from the boiler outlet back to
   138   139   140   141   142   143   144   145   146   147   148