132                                                                               Boiler Operator’s Handbook

               side of a fluid heater is critical to detecting a buildup of  growth of a leak also becomes a factor to consider. The
               carbon in the tubes. Monitoring is not as simple as read-  fluid has to be circulated long enough to allow the heater
               ing the gauges at the inlet and outlet then subtracting  to cool until it will not carburize the fluid left standing in
               the difference. Since viscosity changes with temperature  it. It also has to be cooled enough so it will not spontane-
               you need to have a record of pressure drop at different  ously ignite when exposed to air, then the fluid must be
               average temperatures so you have relative pressure  drained from the system back to storage until the level
               drops for comparison. You want to be as precise as  is below the point of the leak. Some facilities don’t have
               possible with your measurements because you want to  sufficient storage to completely drain their systems and
               catch the carbon formation the instant it starts.    require a supplier’s empty truck, on rental, to hold the
                    Even a very thin coating of carbon is so rough it  fluid as it’s drained.
               can produce a significantly rough surface on the inside     Organic fluid heaters and the occasional vaporizer
               of the tubes so the pressure drop increases significantly.  make some chemical processes possible only because
               That’s usually not a problem because the circulating  they can produce high temperatures at low pressure. A
               pumps are normally positive displacement types that  common application is in the asphalt industry where the
               will continue to force the designed flow of fluid through  product must be heated to high temperatures so it can
               the heater. When carbon builds up failure tends to be  flow readily. All the rules for high pressure boilers apply
               instantaneous because the increased pressure drop is  and every plant will have unique and special provisions
               handled until the pump motor is overloaded and trips  that the operator should know. Among all plants these
               out. Systems with centrifugal circulating pumps are un-  are the ones where the SOPs must be memorized be-
               common because the viscosity variation with tempera-  cause lack of rapid and proper response to an upsetting
               ture has a significant effect on the flow in the system and  condition can lead to hazardous conditions or long-term
               the performance of the pump.                         shutdown of the facility.
                    I did have one customer that solved his problem
               temporarily by installing a larger motor on the pump. It
               was nearly impossible to tell what was going on in the  SERVICE WATER HEATING
               system because none of the pressure gauges worked.
               When they finally got some gages in place a high pres-     Service water is the term currently used by
               sure drop was detected across the heater and they had to  ASHRAE to describe what I always called domestic hot
               shut the whole plant down to retube it.              water heating. Heating of water for cooking, showers,
                    Any organic fluid system should be checked  baths, washing, etc., is not the same as heating water for
               throughout its entire length at least once a shift with  closed hydronic building heating systems so we’ll use
               special attention paid to any signs of leakage. The in-  the term “service water” to describe it.
               sulation is typically calcium silicate in order to handle     Service water heating systems are frequently ig-
               the high temperatures, and it’s also very thick, so a slow  nored. I didn’t think about it much at my home because
               leak can penetrate a lot of insulation (store a lot of fuel)  I have an electric hot water heater and it managed to
               before it’s detected. System leaks are dangerously close  operate trouble free for thirty years. Finally, the plastic
               to becoming fires and they must be caught before they  dip tube failed, disintegrating into thousands of little
               become a fire; there is no steam quenching on the piping  pieces that fouled every faucet and toilet tank float valve
               like there is in the furnace.                        until I was so frustrated I called the water company to
                    Since most organic fluid systems are used in pet-  complain about the junk they put in the water. It was a
               rochemical and similar industrial production plants  little embarrassing to have them tell me it was probably
               immediate shutdown to repair a leak could result in  the dip tube then discover that was the case. Anyway, I
               thousands of dollars of production loss so you may be  figure my new electric hot water heater and it’s dip tube
               compelled to simply monitor a minor leak and be pre-  will outlive me.
               pared to extinguish any fire that results until the entire     I wish you were all that lucky. It won’t happen very
               facility can be economically shut down. It’s one of those  often. Service water heaters do not enjoy the presence of
               situations where the operator has to consider multiple  chemically treated water to prevent scale and corrosion
               risks and the cost of each; any leak that can’t be made  and most of them have such problems. I remember one
               up, or becomes extensive to the degree it’s a dramatic  area where the well water contained so much calcium
               hazard, requires a shut down.                        sulphate that it would form heavy scale if the water tem-
                    Shutting  down  a  fluid  system  takes  time  so  the  perature was increased by 6°F. There’s nothing you can