Page 220 - Boiler_Operators_Handbook,_Second_Edition
P. 220

Maintenance                                                                                         205


                    Any discussion about insulation raises the concern  ity a light canvas wrap impregnated with a waterproof
               for asbestos bearing insulation contaminating the air in  mastic will look better and will last even longer.
               the plant. While many facilities have spent the fortune it     Outdoors and in areas where the insulation may
               costs to remove asbestos bearing insulation others have  be struck by people carrying objects such as ladders the
               chosen to encapsulate it. If your plant is one of the latter  corrugated aluminum jacket with aluminum straps and
               then maintenance of that encapsulation has a priority.  fasteners is necessary to provide long life. Long runs of
               Damage to the cover can occur as a result of normal  hot piping pose a special problem, the pipe expands but
               operating and maintenance activities, from vibration  the insulation doesn’t expand anywhere near as much.
               that occurs during normal operation or a plant upset.  And the jacket, particularly outside in cold weather, can
               A tour to check the integrity of encapsulation should be  shrink from its original length. When restoring insula-
               performed on a monthly basis.                        tion on long runs try to compress the existing insulation
                    When it becomes necessary to gain access to some-  as much as possible without crushing it then compress
               thing covered by Asbestos insulation you should notify  the new material as much as possible when installing it;
               your employer so he can have the insulation removed  jackets should have a minimum overlap of three inches
               unless you have been trained to do it. The laws regard-  outdoors and the longitudinal seam should always be
               ing asbestos bearing insulation do permit removal of  on the side of the piping lapped down to prevent rain
               small quantities without all the environmental controls  entering the seam. On vertical runs of pipe make certain
               required of a major material removal; and you could be  any jacketing is lapped to shed water. Do it indoors too
               trained to do it. If you are, follow the rules you were  because a leak can always spray water, or worse, all over
               taught in the class. If not, and you think the contractor  the place.
               doing the removal is contaminating your air (lots of dust     Large flat surfaces require the installation of insu-
               blowing around isn’t to be accepted) scream and holler  lation studs, wire secured to the surface by stud weld-
               because once you’ve breathed it in it’s yours for a life-  ing or a special machine that shoots the wire into the
               time. Once the work is complete make sure the asbestos  surface. The studs hold insulation with special washers
               that remains is encapsulated and don’t forget to mention  over the stud pressing the insulation against the equip-
               its removal, and who did it, in the boiler plant log.  ment surface. An impregnated canvas covering or cor-
                    Whenever insulation is removed for maintenance  rugated aluminum jacketing is necessary to protect the
               or repair make certain it’s put back or replaced. I, if no-  surface of that insulation. Any repair job should return
               body else, will have a very low opinion of your mainte-  the insulation to a like new condition using one of the
               nance practices if I come into the plant and find little bits  methods I described.
               of insulation missing here and there. Small areas tend     What do you do if some insulation gets wet? If it
               to become bigger and, after a while, the whole system  got so wet that it collapsed it has to be replaced, other-
               is bald. Not only is it a waste of energy, it’s hazardous  wise let it dry. If it got wet while the pipe was out of ser-
               because you could be severely burned.                vice and the line contains steam or hot water you should
                    I was in one plant where I suggested the customer  warm the piping up very slowly or you may generate
               do something about his insulation for another safety  steam under the insulation that will blow it off.
               reason. It had received no attention and was literally     Damaged or compressed insulation should be re-
               falling off the pipes. The hazard was associated with be-  placed as part of the annual clean up operation. Where
               ing hit on the head by falling insulation! Such instances  the damage is repeated some consideration should be
               aren’t uncommon and they lead me to recommend you  given to installation of better protection of the insula-
               never accept an insulation job that consists of nothing  tion, consider replacing or covering the jacket with
               but stapling up ASJ (All Service Jacket, that white paper  heavy galvanized sheet metal thick enough to ward off
               like material with the flap that comes on most insula-  the damage.
               tion) because it won’t last. The staples eventually cor-     No,  I  don’t want  to  hear  the  argument that  it
               rode and fail with the rest of what happens being most  doesn’t make any difference if the piping is only used
               obvious.                                             during the heating season and it heats the building any-
                    At the very least piping insulation should be  way. The heat lost through lack of insulation is almost
               secured with minimum 20-gauge galvanized wire  never able to heat the space as intended. It’s almost as
               wrapped around it, twisted, and bent back against the  weak an argument as the one that I’m always hearing
               insulation (to prevent the sharp ends catching or cutting  which is “it’s only a little bit.” Little bits become lots
               anything or anyone) twice on each section. For longev-  when that attitude is taken. “We’re out of that thick-