Page 236 - Boiler_Operators_Handbook,_Second_Edition
P. 236

Maintenance                                                                                         221


               be removed.
                    Once you’ve removed the tube you should “dress
               up” the hole, removing any tube metal stuck to it and
               any corrosion that would accompany a leak or defective
               rolled joint. Careful use of a file and sandpaper should
               produce a smooth surface. The edges of the holes should
               also be smoothed over to eliminate any sharp edges
               that will cut the new tube. The tube ends should also be
               dressed up to remove any corrosion for a tight metal to
               metal fit.
                    The new tube is expanded with a roller (Figure
               6-11a) to compress the outside of the tube against the
               inside of the tube hole to seal the joint. The roller in
               Figure 6-11a expands the end of the tube inside the           Figure 6-12a. Rolled tube—flared
               boiler, flaring it. The roller in Figure 6-11b has a beading
               attachment which forces the metal end of the tube out
               and back against the tube sheet to form the ends shown
               in Figure 6-12b. As shown in Figures 6-12 of completed
               joints a water tube, Figure 6-12a is flared but a fire tube
               end is beaded; Figure 6-12b or restricted in protrusion to
               limit heating of the end of the tube. Typically the inlet
               of the first pass of a four-pass firetube boiler is welded
               (6-12c) to increase its ability to transfer heat to the water
               because the flue gases are much hotter in that first turn
               of a four pass boiler.
                    Once your tube replacement is complete the boiler
               should be subjected to a full one and one-half times
               maximum allowable working pressure hydrostatic test.
               Many contractors and most inspectors will accept an
               operating pressure test but why accept anything other
               than a test that proves the repair has returned the boiler
               to a like-new condition?                                     Figure 6-12b. Rolled tubes—beaded
                    Refer to the section on hydrostatic testing a new
               boiler. Testing a repaired boiler is done the same way.






















               Figure 6-11a.  Tube  Figure 6-11b. Tube roller bead-
               roller with flare     ing attachment

                                                                            Figure 6-12c. Rolled tubes—welded
   231   232   233   234   235   236   237   238   239   240   241