Page 27 - Boiler_Operators_Handbook,_Second_Edition
P. 27

12                                                                                Boiler Operator’s Handbook


               3 to 2 turndown must be a novice in the industry) mini-  ing (looking along the length of an edge with your eye
               mum operating rate is determined by dividing the larger  close to it) is the best way to check to confirm an edge is
               number into one. If you run into the nut that described a  straight.
               3 to 2 turndown then the minimum capacity is 2/3 of full     For measures larger than something you can check
               capacity. Divide the large number into one and multiply  with that square you should use a 3 by 4 by 5 triangle;
               by 100 to get the minimum firing rate in percent.    the same thing the Egyptians used to build the pyra-
                    We  also  use  the  term  “load”  when  describing  mids. You lay it out by making three arcs as indicated in
               equipment operation. Load usually refers to the demand  Figure 1-1. You frequently also need a straight edge as
               the facility served places on the boiler plant but, within  the reference that you’re going to be square to, in which
               the correct context, it also implies the capacity of a piece  case you mark off 3 units along that edge to form the one
               of equipment to serve that load. If we say a boiler is  side, that’s drawing the arc to find the point B by mea-
               operating at a full load that means it is at its maximum;  suring from point A. An arc is made 4 units on the side at
               half load is 50%, etc.                               point C by measuring from point A then another arc of 5
                    A less confusing but more difficult measure to  units is made measuring from point B and laying down
               address are “implied” measures. Some are subtle and  an arc at D. Where the A to C and B to D arcs cross (point
               others are very apparent. A common implied measure  E) is the other corner of the 3 by 4 by 5 triangle and side
               in a boiler plant is half the range of the pressure gauge.  A to B is square to A to E. The angle in between them is
               Engineers normally select a pressure gauge or thermom-  precisely 90 degrees.
               eter so the needle is pointing straight up when the sys-     The beauty of the 3 by 4 by 5 triangle is the units
               tem is at its design operating pressure or temperature.  can be anything you want as long as the ratio is 3 to 4 to
               We always assume that the level in a boiler should be  5. Use inches, or even millimeters, on small layouts, and
               at the center of the gauge glass, that’s another implied  feet on larger ones. If you were laying out a new storage
               measurement. In other cases we expect the extreme of  shed you might want to make the triangle using 30 feet,
               the device to imply the capacity of a piece of equipment;  40 feet, and 50 feet. It’s difficult to get more precise, even
               steam flow recorders are typically selected to match the  if you’re using a transit.
               boiler capacity even though they shouldn’t be. The prob-     Another  challenge  is  finding  a  45  degree  angle.
               lem with implied measurements is that we can wrongly  The best solution for that is to lay out a square side to
               assume they are correct when they’re not. Keep in mind  get that 90 degree angle then divide the angle in half.
               that someone could have replaced that pressure gauge  Figure  1-2  shows  the  arrangement  for  finding  half  an
               with something that was in stock but a different range.  angle. Simply measure from the corner of the angle out
               I failed to make that distinction one day and it took two  to two points (C and D) the same distance (A to B) then
               hours of failed starts before I realized the gauge must be  draw two more arcs, measuring from points C and D a
               wrong and went looking for the instruction book. Yes,  distance E, and F identical to E to locate a point where
               I’ve done it too.                                    the arcs cross at G. A line from A to G will be centered
                    Probably one of the most common mistakes I’ve
               made, and that I’ve seen made by operators and con-
               struction workers, is not getting something square. All
               too often we’ll simply eyeball it or use an instrument
               that isn’t adequate. The typical carpenter’s square, a
               piece of steel consisting of a two foot length and sixteen
               inch length of steel connected at one end and accepted
               as being connected at a right angle works well for small
               measurements but using it to lay out something larger
               than four feet can create problems. I say “accepted as
               being square” because I’ve used more than one of them
               to later discover they weren’t. Drop a carpenter’s square
               on  concrete  any  way  but  flat  and  you’ll  be  surprised
               how it can be bent. On any job that’s critical, always
               check your square by scribing a line with it and flipping
               it over to see if it shows the same line. Of course the
               one side you’re dealing with has to be straight. Eyeball-     Figure 1-1. Creating a right angle
   22   23   24   25   26   27   28   29   30   31   32