Page 170 - Boiler plant and distribution system optimization manual
P. 170

Over 100 Ways to Improve Efficiency                                                              155



                a year savings with HTW. Over a life cycle of 25         In Europe energy engineers have come up
                years the savings was over $14 million.             with the rule of thumb that it takes 49 times more
                                                                    energy to move a unit of thermal energy from
                                                                    point A to point B than to move the same ener-
                12.  SATELLITE BOILERS                              gy  as  fuel.  This  may  not  be  the  specific  case  in
                                                                    all applications, but it is definitely something to
                Cost                                                consider in the case of satellite boiler projects in
                     Moderate to High                               old central steam systems.


                Potential Savings                                   Advantages/Disadvantages
                     Very High                                           The cost of installing satellite boilers and the
                                                                    permitting process can be quite high, but the sav-
                Description                                         ings can be very high in both maintenance costs
                     Once during the days when coal was King and    and in energy savings.
                after Heavy Fuel Oil took its place, large central
                plants and  extensive steam  distribution systems
                were built to accommodate the central fuel supply   13.  ADJUSTABLE SPEED DRIVES
                and need for skilled plant operators for safety and
                                                                    Cost
                reliable operations on a 24 hour basis month after
                                                                         Moderate
                month year after year. Distribution system losses
                can be very high and it has been found the best
                                                                    Potential Savings
                way  to  eliminate  distribution  system  losses  is  to
                                                                         Moderate to high.
                eliminate the distribution system. Originally, cen-
                tral plants were designed around the use of coal
                                                                    Description
                because  it  was  the  only  fuel  available  and  now
                                                                         When pumps and fans operate at higher rpms
                many facilities have miles of old and questionable
                                                                    than required for a particular load, electrical en-
                distribution systems which were built before the
                                                                    ergy is lost. The pump and fan laws apply which
                day of the reliable and safe satellite boilers. When
                                                                    states that the energy used varies with the cube of
                you see brown grass above buried steam lines in
                                                                    the rpm. Large savings can be accomplished by
                the  summer  and  melted  snow  over  the  distribu-
                                                                    reducing the rpm of rotating equipment. Variable
                tion system in the winter, you are probably looking
                                                                    speed drives are a new dimension in the cost ef-
                at heat losses from buried steam and condensate
                                                                    fective management of plants. For example, if the
                piping. Every foot of piping is a possible source
                                                                    speed of a pump or fan is reduced by one half,
                of leaks, energy  losses, acid corrosion and other
                                                                    there is a 88% reduction in energy use.
                maintenance problems. Rain soaked and degraded
                insulation,  flooded  systems,  steam  plumes  along
                                                                    Advantages/Disadvantages
                the steam mains in streets and fields and cold or
                                                                         Many plants have successfully applied ad-
                lost condensate are all indicators of major distribu-
                                                                    justable speed drives to boiler operations.  Ad-
                tion system problems.
                                                                    justable Speed Drive (ASD) is becoming a proven
                     The central steam plant can be a huge lia-
                                                                    way to save electrical costs.
                bility; one only has to analyze steam production
                during warm weather or holidays to discover that
                large losses exist. Reliable and safe control tech-
                                                                    14.  CONVERT TO INFRARED HEATERS
                nology and the availability oil and gas supplies
                now make individual satellite boilers a safe and
                                                                    Cost
                efficient way to avoid these large distribution sys-
                                                                         Moderate
                tem losses.
   165   166   167   168   169   170   171   172   173   174   175