Page 264 - Boiler plant and distribution system optimization manual
P. 264

Steam System Optimization                                                                         249
























                                               Figure 13.2—Flash Steam Energy Balance.


                the rest is lost through the trap. If we were able   Table 13.2 shows why steam pressure should be
                to drop the working pressure on a piece of equip-   reduced at the point of use. It conserves the loss of
                ment from 125 psig to 5 psig, the latent heat would   energy through the steam trap.
                be 83.5% of the total energy instead of 73.5%.      ———————————————————————
                                                                                         Latent          Percent
                     Significant steam savings can be realized by
                                                                         Pressure         Heat           of Total
                reducing steam pressure as low as possible using
                                                                           psig          Btu/lb           Heat
                pressure reducing valves in new as well as exist-
                                                                    ———————————————————————
                ing installations.
                                                                           125            868             73.5
                     As shown in Table 13.3, the percent heat sav-
                ings available from reducing pressure is signifi-           50            912             77.5
                cant. For example, there will be a 13% savings by
                reducing the pressure from 150 to 20 psig.                   5            961             83.5
                                                                    ———————————————————————

                A Rule of Thumb for Optimizing Steam                Table 13.3—Heat savings available from  reducing
                System Pressure                                     pressure  at the  point  of use.  (To calculate  these
                ————————————————————————                            numbers, flash steam reduction and the latent heat of
                a.   System steam pressure should be distribut-     the steam and the heat in the condensate at the old and
                                                                    new pressure is considered)
                     ed at high enough pressure as is practical to
                                                                    ———————————————————————
                     overcome line losses and satisfy the highest
                                                                                           Original Pressure
                     pressure user.
                                                                                                (psig)
                                                                         Reduced     125         150        200
                b.   Steam pressure should be reduced at the
                                                                         Pressure         (Steam Savings %)
                     point of use to as low a pressure as is practi-  ———————————————————————
                     cal.
                ————————————————————————                                 100 psig     2.1         3.6        6.8
                                                                         75 psig      4.4         5.9        9.0
                     Two general points to consider in the steam
                distribution system is, design requirements limit        50 psig      7.2         8.6       11.6
                steam velocities to less than 6,000 to 12,000 feet
                per minute and the system pressure drop should           20 psig     11.5        13.0       15.8
                not exceed 20 percent of the total maximum pres-
                                                                         10 psig     13.7        15.0       17.8
                sure of the boiler.
                                                                    ———————————————————————
   259   260   261   262   263   264   265   266   267   268   269