Page 65 - Boiler plant and distribution system optimization manual
P. 65

50                                                  Boiler Plant and Distribution System Optimization Manual


                 ———————————————————————                                 For the planner and designer, eliminating
                   When conditions are not observable or known,     life cycle system losses should be a primary con-
                         the assumption is often made that          cern right from the drawing board. For the main-
                                they are negligible .               tenance force, pipe insulation, steam trap testing
                                                                    and repair, steam leak prevention, and conden-
                        In steam systems most of the losses         sate recovery system maintenance can have a
                                are not observable.                 significant impact on operating costs. In the boiler
                         Unfortunately, the losses are quite        plant monitoring the amount of make up water
                           large and jar from negligible.           and the condensate return temperature are im-
                 ———————————————————————                            portant indicators of the health of the distribution
                                                                    system. If the pure hot water is not brought back
                     In  this  chapter  we  have  examined  infor-  to the plant by the condensate recovery system,
                mation  about  various  ways  steam  distribution   then the expense of new water, chemical treat-
                systems  control  and  ultimately  waste  energy    ment and heating it to operating temperature will
                including various energy loss mechanisms and        just add to avoidable plant expenses.
                their relative costs.

                                                      Loss Summary


                       Distribution System Losses                         Percent             Dollars/yr

                       Insulation Losses
                            600 psi (10,000 ft.)                            1.90%               $82,344
                            175 psi (4,000 ft)                              0.46%               $19,763
                            Condensate Recovery sys (10,000 ft)             0.57%               $24,703

                       Flash Steam Load
                            600 psi (surface losses)                        0.91%               $39,522
                            175 psi (surface losses &                      11.14%               $481,514
                                75,000 pph load)

                       External Steam Leaks                                 1.94%               $84,000
                       Internal Steam Leaks                                 0.61%               $26,556
                       Steam Trap Failures                                  1.43%               $61,964
                                                                          ————               —————
                                                                           18.51%               $820,360

                       What If
                       (1)   All steam piping were bare:
                            600 psi system surface losses                  32.38%             $1,399,848
                            600 psi flash losses                           33.32%             $1,440,585
                            175 psi system surface losses                   4.57%               $197,626
                            175 psi flash losses                           15.75%               $680,869
                                                                          ————               —————
                                                                           86.02%             $3,718,928

                       (2)   Condensate Recovery System
                            A 55 F [13C] drop
                                in system Temperature                       4.76%               $242,131

                       (3)   No condensate returns
                            100% make up @ 62F [17C]                       11.43%               $581,115
   60   61   62   63   64   65   66   67   68   69   70