Page 63 - Boiler plant and distribution system optimization manual
P. 63

48                                                  Boiler Plant and Distribution System Optimization Manual


                     ed with steam systems, such as steam trap      $20,000. Flash steam losses are much less at 72,000
                     flash losses, steam trap malfunctions [often   Btu per hour, worth about $3,000 a year.
                     as high as 40%], packing gland leakage, wa-
                     ter hammer damage and high temperature
                     stresses caused by rapid temperature chang-    FLASH STEAM LOSSES
                     es.
                                                                    FROM INSULATION LOSSES
                3.   Because of the higher heat content, piping
                     sizes are smaller saving on construction            There  is  another  significant  loss  resulting
                     costs.                                         from the  insulation  losses.  When  steam  in  the
                4.   On the down side, pumps are required to cir-   piping  loses  energy  through  the  pipe  wall,  it
                     culate the hot water throughout the system.    condenses then goes through the steam trap as
                                                                    water. In this case of the 600 psi steam, the water
                                                                    temperature will drop from 489F to 212F across
                INSULATION LOSSES                                   the trap.
                                                                         The Btu content of the water at 600 psi is 475
                     All sections of hot pipe, valve bodies, unions,   Btu per pound before the trap and is only 180
                flanges and most steam traps should be insulated.   Btu/lb on the low pressure side of the trap. At
                Insulation will pay for itself quickly, less than one   atmospheric pressure, 970 Btus/lb are required to
                half year, as well as prevent the overheating of    form a pound of steam. This results in about 30.
                working spaces and the elimination of hot and       4% flash steam.
                dangerous surfaces.                                      With an average surface loss of 200 Btu per
                     Steam  users  should  be  fully  aware  of  the   lineal ft for 10,000 ft [3050 meters] of piping, in-
                need to insulate hot surfaces but it takes constant   sulation losses from the 600 psi system will form
                vigilance to keep steam systems in good condi-      2,743 pounds of water per hour. One pound of
                tion.                                               water forms for each 729.1 Btu lost from the pipe.
                     In  our  example  we  have  10,000  ft  [3,050   So, with the 30.4% flash rate, 834 pounds of steam
                meters] of well insulated piping which has an av-   per hour will be produced. This steam will have
                erage heat loss of 200 Btus per lineal ft per hour,   a heat value of 1120 Btu/lb. If this flash steam is
                this works out to 2 million Btus per hour which is   lost through atmospheric vents it will cost $39,522
                1.9% of the system load costing $82,344 a year.     a year.
                     Our system also includes 10,000 feet [3,050
                meters] of condensate return piping plus a num-
                ber of tanks and pumps. The criteria for surface    BARE PIPING LOSSES
                temperature of insulated piping us generally
                agreed to be about 140F [60C], so in the case of         If the 600 psi [40 Bar] piping system were not
                condensate return piping insulation is often not    insulated but bare, it would lose about 3,400 Btu
                used because it is uneconomical and the surface     per lineal foot rather than 200 Btu per ft, a factor
                temperature will not normally exceed 140 F [60C].   of 17 greater. In the 175 psi [12 Bar] system the
                Under these conditions,  surface  losses  will  be   value for bare pipe is 1200 Btu per lineal ft per
                about 60 Btu per lineal ft per hour. For our ex-    hour compared to 120 Btu for economical insu-
                ample, this loss will be 0.6 million Btus an hour   lation. The increase of losses from bare pipe is a
                costing 24,700 a year.                              factor of 10 greater than economical insulation.
                     In the 4,000 ft [1,220 meter] system at 175 psi,      The North American Insulation Manufactur-
                because of lower temperatures and Btu values,       ers Association (NAIMA) has developed software
                the losses are less; 120 Btu per lineal ft. The insu-  applications to calculate heat losses from bare
                lation losses in this section are about half a mil-  pipe and for various combinations of insulation.
                lion Btus per hour with an annual cost of about     This software solves these problems rather handi-
   58   59   60   61   62   63   64   65   66   67   68