Page 62 - Boiler plant and distribution system optimization manual
P. 62

Distribution System Efficiency                                                                     47



                FLASH STEAM                                              This is why high pressures are used in dis-
                                                                    tribution systems and pressure reducing valves
                     The largest energy loss in steam systems is    (PRV) are used close to the point of use of the
                flash steam in open condensate recovery systems.    steam.
                When the hot condensate passes through a trap            Let’s look at an open system, in this case
                from a high energy level to a lower energy level    the 175 psi [12 Bar] steam system in our example
                and percentage of the water flashes into steam.     which is delivering steam to the points of use.
                Figure 5.3 illustrates this energy balance across a   Assuming there is a load on this system of 75,000
                steam trap.                                         pounds of steam per hour passing through steam
                                                                    traps, the flash rate is about 17%. This will pro-
                                                                    duce 12,000 pounds of flash steam per hour cost-
                                                                    ing over $480,000 a year. This is an 11% system
                                                                    loss.
                                                                         This  is  a  basic  problem  of  these  systems,
                                                                    flash steam losses as great as total boiler plant
                                                                    losses. High temperature hot water systems do
                                                                    not have a number of problems associated with
                                                                    steam systems.


                Figure 5.3—Flash steam forms on the low pressure
                                                                    HIGH TEMPERATURE HOT WATER SYSTEMS
                side of the steam trap, in this case with almost 3
                times as much energy as the condensate.
                                                                           High temperature water distribution sys-
                                                                    tems are divided into three categories:
                     The formula for flash steam is simple; the
                difference in enthalpy [Btu/lb] of the water on     1.   High Temperature Hot water systems have a
                either side of the steam trap is divided by the Btus     temperature range from 350 F [177C] to 450
                required to form a pound of steam at the lower           F [232C).
                pressure.                                           2.   Medium  Temperature  Hot  water  systems
                                                                         have  a  temperature  between  250  F  [121C]
                       475 – 180                                         and 350F [l77C].
                        ————  = 30.4% Flash Steam
                          970                                       3.   Low  Temperature  Hot  water  systems  are
                                                                         usually below 250F [121C].
                     All steam used by the system must pass
                through  steam  traps,  so  the  whole  system  is       It is interesting to note that one cubic foot of
                subject to this loss if atmospheric vents are used.   hot water at 350F contains 64 times as much heat
                Closed pressurized condensate recovery systems      as a cubic foot of saturated steam at 350F [177C].
                are  used  in  well  designed  plants  to  avoid  this   When  high  temperature  hot  water  cools  from
                problem.                                            350F to 25°F, it releases 40 times more heat than a
                     Flash steam percentages vary with pressure     cubic foot of steam.
                drop across steam traps, for example exhausting          Other  features  of  high  temperature  water
                to an open (atmospheric) system:                    systems are:

                                                                    1.   High Temperature Water systems are closed
                   —————————————————————
                                                                         systems and should only use one half of one
                           600 psi trap has a 30% flash                  percent make up water compared to boilers
                           175 psi trap has a 17% flash                  which use quite a lot; in some cases 100%.
                            50 psi trap has a 4% flash
                                                                    2.   They do not have the usual losses associat-
                   —————————————————————
   57   58   59   60   61   62   63   64   65   66   67