Page 303 - Chemical process engineering design and economics
P. 303

282                                                      Chapter 6

           volume  of the  dished heads  is not  considered  in the procedure. Knock-out drums
           are mostly installed  in a vertical position.  Younger  [11] found  that out of  eleven
           drums installed in several plants, nine were vertical.



           Table 6.7  Summary of Equations for Sizing Knock-Out Drums_______

           Subscripts: L = liquid — V = vapor
                  fp '-pv'Y /2
                    L
                  I—————    I                                          (6.7.1)
           v v = k v
                  I  Pv'   >/
           k v = 0.2  ft/s  (0.061 m/s) —  with no mist eliminator     (6.7.2)
           k v = 0.35  ft/s  (0.107 m/s)  —  with a mist eliminator
           V v '=v v A                                                 (6.7.3)

                  2
           A =  ?t D /4                                                (6.7.4)

           L/D = 2                                                     (6.7.5)

           Variables
           V y - k y - A - D - L




           Table 6.8  Calculation Procedure for Sizing Knock-Out Drums_______

            1. Select a value of k v from Equation 6.7.2.

           2. Calculate a maximum gas velocity, v v, from Equations 6.7.1.

           3. Calculate the cross-sectional area of the separator, A, from Equation 6.7.3.

           4. Calculate the diameter, D, of the separator from Equation 6.7.4.

           5. Round off  D in 6 in (0.152 m) increments, starting at 30 in (0.762 m). If  D is
           less then 30 in (0.762 m), use standard pipe.

           6. Calculate the length of the separator from  Equation 6.7.5. Round  off  L in 3 in
           (76.2  mm) increments, for example, 5.0, 5.25, 5.5, 5.75 ft, etc.




         Copyright © 2003 by Taylor & Francis Group LLC
   298   299   300   301   302   303   304   305   306   307   308