Page 307 - Chemical process engineering design and economics
P. 307

286                                                     Chapter 6

            Table  6.10  Calculation  Procedure  for  Sizing Vertical  Gas-Liquid  Separa-
            tors______________________________________

            1. Select k v from Equation 6.9.3.

            2. Calculate the maximum gas velocity, vy, from Equations 6.9.2.

            3. Calculate the cross-sectional area, A, from Equation 6.9.1.

            4. Calculate D from Equation 6.9.4.
            5. Round  off D  in  6 in (0.152  m) increments,  starting  at  30  in (0.762  m).  If D is
            less than 30 in (0.762 m), use standard pipe.

            6. Select a liquid-phase surge time, ts, from Equation 6.9.6.

            7. Calculate the liquid-level height from Equation 6.9.5.
            8.  Calculate  the  total  separator  height  from  Equation  6.9.7.  Round  off L  in  3  in
            (0.0762 m) increments, for example, 5.0,  5.25,  5.5,  5.75  ft etc.

            9. If L/D < 3.0,  then recalculate L so that L/D > 3.0 by letting L/D = 3.2.  If L/D >
            5 use a horizontal separator.





            increase L in order that L/D > 3, even if the liquid  surge volume  is increased. In-
            creasing the surge volume is in the right direction.

            Horizontal Gas-Liquid Separators

            Like vertical gas-liquid separators, there are several design procedures reported in
            the  literature -  not all of them are in agreement. A schematic diagram of a hori-
            zontal  gas-liquid  separator  is  shown  in  Figure  6.5.  For  horizontal  separators,  the
            calculation procedure  for  sizing  is  essentially  the  same  as  vertical  separators  ex-
            cept  increase k v  by  25  %  [49].  Also,  the  minimum  value  of  the  cross-sectional
            area  for  gas  flow  should  be  at  least  20  %  of  the  total  cross-sectional  area  of  the
            separator  [49].  Use  a  6  in  (0.152  m)  mist  eliminator  and  a  distance  of  12  in
            (0.3048m)  above  the eliminator. According to  Gerunda  [4],  the  distance from  the
            bottom  of the  mist  eliminator  to the  liquid  level  should be  at  least 2 ft (0.610 m)
            and should not be below the center of the  separator.  Scheinman  [72] recommends
            6  in  (0.152  m).  Use  an  average  of  1.25  ft. The  main  consideration  is  to prevent





         Copyright © 2003 by Taylor & Francis Group LLC
   302   303   304   305   306   307   308   309   310   311   312