Page 321 - Decision Making Applications in Modern Power Systems
P. 321

282  Decision Making Applications in Modern Power Systems























            FIGURE 11.1 Schematic diagram of LFC/AGC system. AGC, Automatic generation control;
            LFC, load-frequency control.

            strategy, which can be deployed in real-time operation, can be computed
            simultaneously.
               This strategy makes use of the distribution vectors. Depending on the out-
            age magnitude and the wind power deviation, the amount of power by which
            each generating unit should adjust its production can be determined. The pro-
            posed methodology is an alternative to other methods for reserve scheduling,
            which account implicitly for real-time response via their day-ahead deci-
                                        i
            sions. A power correction term R is defined as a piecewise linear function
            of the total generation-load mismatch. This term shows the amount of the
            power that each generator should compensate for given an imbalance and is
            directly related to the reserves.
                                                      i
                  i
                                   i




                 R P w Þ 5 d i  max 2P P w Þ 2 d i  max P P w Þ ;  iAϒ  ð11:1Þ
                  ð
                                    ð
                                                       ð
                         up        m        down      m
                             1                   1
            where max 1 (   ) 5 max(   ; 0). Variable P m Aℜ denotes the generation-load
            mismatch, which for each outage is given by
                         X           f      i     i     i
                i
               P P w Þ 5      P w;k 2 P  2 c P L 1 c P G 1 c P w ;  for all iAϒ
                 ð
                m                    w;k    L     G     w
                        kAZ w =K  i
                                                                      ð11:2Þ
               d up ; d down Aℜ NG  are the distribution vectors. The sum of these elements
            must be equal to one and, if a generator is not contributing to the AGC, the
            corresponding element in the vector will be zero. To distinguish between up-
            spinning reserves and down-spinning reserves, the indices “up” and “down”
            are used. If P m is negative, up-spinning reserves are provided, and the pro-
            duction of the generators is increased accordingly. In the opposite case the
            second term of (11.1) is active, and down-spinning reserves are provided. It
   316   317   318   319   320   321   322   323   324   325   326