494  Decision Making Applications in Modern Power Systems





























            FIGURE 18.10 Performance of WPE_BDT-3 and -4 modules for detection and classification
            of shunt fault (double phase to ground fault-A1B1G): (A) Three phase instantaneous currents of
            circuit-I (B) Three phase instantaneous currents of circuit-II (C) Three phase instantaneous vol-
            tages at sending-end bus (D) Fault detection using WPE_BDT-3 module (E) Fault classification
            using WPE_BDT-4 module. WPE_BDT, Wavelet packet energy and bagged decision tree.





              TABLE 18.10 Response of wavelet packet energy and bagged decision
              tree-3 and 4 modules for detection and classification of shunt faults
              during the power swing.

                     Type  Δδ       Fault    Fault classification time (ms)
                     of    (degrees)  detection
                                             A1   B1  C1   G   A2   B2  C2
                     fault          time (ms)
              Shunt  AG    105      14.0     14            14
              faults
                     ABG   110      22.0     22   22       22
                     AB    115      22.0     22   22
                     ABC   120      18.0     18   18  18   18
              Shunt  AG    105      14.0     14            14
              faults
                     ABG   1 10     24.0     24   24       24
              (power
              swing)  AB   115      17.0     17   17
                     ABC   120      19.0     19   19  19