Page 30 - Defrosting for Air Source Heat Pump
P. 30

Previous related work: A review                                    23

           units, the heating source should come from waste heat, such as the heat recovered from
           exhausted indoor air or waste hot water. However, the application of this
           frost-suppression measure is also limited due to the disadvantages of high running cost
           and inconvenience.
              Although the energy consumed for frost suppression is carried over by the refrig-
           erant circulated in an ASHP system, it is actually input into the system. This measure
           is essentially different from external measures such as increasing the inlet air temper-
           ature or decreasing the inlet air RH, where the energy is carried away by the inlet air.
           As listed in Table 2.3, the evaluation results of 11 classical frost-suppression measures
           are given. Nearly all the measures would increase the initial cost and/or the running
           cost, except the two measures of adjusting the fin and tube geometry and the fin type.
           Adjustment and optimization would increase the system complexity and decrease sys-
           tem stability. Additional thermal energy is needed for the measures of preheating the
           inlet air and employing an external heat source. Four measures require floor space for
           additional equipment, such as a desiccant bed for reducing inlet air humidity and an air
           jet or ultrasonic vibration facility to destroy frost formation or growth. Among all the
           measures, reducing the inlet air humidity and preheating the inlet air have the best
           frost-suppression effect. Among all measures listed, preheating the inlet air with waste
           heat and putting a coating treatment on the fin surface with new coating materials are
           highly recommended, due to both having the highest evaluation index in Table 2.3.


           2.3   Defrosting methods for ASHP units

           As discussed earlier, the presence of frost on the surface of the outdoor coil in an
           ASHP unit would deteriorate its operating performance, energy efficiency, reliability,
           and lifespan. While the use of frost-suppression measures can delay or reduce frost
           formation or growth, these measures can be expensive or consume additional energy,
           and there will still be frost to be removed. Therefore, periodic defrosting becomes nec-
           essary for guaranteeing the satisfactory operation of ASHP units. To distinguish frost
           suppression from defrosting, the differences between the two are summarized in
           Table 2.4.
              In this section, various defrosting methods are reviewed based on the assumption of
           normal frosting operation, where no frost-suppression measures are implemented dur-
           ing heating/frosting. Generally speaking, there are five types of defrosting methods:
           (1) compressor shutdown defrosting, (2) electric heating defrosting, (3) hot water
           spraying defrosting, (4) hot gas bypass defrosting, and (5) reverse cycle defrosting.
           In order to clearly show the differences for the five defrosting methods.


           2.3.1 Compressor shutdown
           For the compressor shutdown defrosting (CSDD) method, ambient air is used as the
           heat source for defrosting. Therefore, it is normally applied to where the ambient air
           temperature is not lower than 1°C. When defrosting is needed, the compressor is shut
           down but the outdoor coil air fan continues to move the ambient air at >1°C to pass
   25   26   27   28   29   30   31   32   33   34   35