Page 184 - Design and Operation of Heat Exchangers and their Networks
P. 184

172   Design and operation of heat exchangers and their networks


          plate spacing. The Fanning friction factor for the single-phase flow is
          given by
                                   f sp ¼ 6:431Re  0:25              (4.140)

             By means of the dimensional analysis, they proposed the evaporation
          heat transfer and pressure drop correlations as

                αd h,b
           Nu ¼
                 λ l
                                         !  0:1        0:5      1:1       2
                                                2
                                    G 2        ρ Δh v      ρ σ      ρ l
                                                            l
                           0:1  2
                       0:5
                                                l
              ¼ 0:603Re lo  Pr l  _ x
                                   2
                                  ρ c p,l ΔT    G 2       η G     ρ  ρ v
                                                           l
                                                                   l
                                   l
                                                                     (4.141)
             The evaporation friction factor is correlated as
               Δp f ρ d h,b        4    0:35   1
                   m
            f ¼         ¼ 3:521 10 Re  lo  Re eq  440   Re eq   3200  (4.142)
                    2
                 2G L
          where Re lo and Re eq are calculated with Eqs. (4.105), (4.106), respectively.
             Huang et al. (2007) compared their field measurement data of plate heat
          exchangers with some available correlations and found that these correlations
          are likely to become inaccurate outside their original ranges. For large-scale
          PHE thermosiphon evaporators (flooded operation model), Cooper’s pool
          boiling correlation (Cooper, 1984) appears to predict the heat transfer coef-
          ficient quite accurately. The comparison among three well-known correla-
          tions was studied by Garcı ´a-Cascales et al. (2007) and compared with the
          Cooper correlation. Large deviation among them can be observed.
          4.2 Condensation

          4.2.1 Condensation on vertical plate
          The laminar film condensation on a vertical plate with constant wall tem-
          perature was first analyzed by Nusselt (1916), which results in the local Nus-
          selt number as

                                                      1=3
                                      α x l  1 ρ =ρ l
                                                 v
                             Nu x,lam ¼  ¼                           (4.143)
                                      λ f     3Re x
          where the characteristic length
                                           2    1=3
                                          μ
                                     l ¼   l                         (4.144)
                                         gρ 2
                                           l
   179   180   181   182   183   184   185   186   187   188   189