Page 222 - Design of Reinforced Masonry Structures
P. 222

4.86                       CHAPTER FOUR

              span plus 8 in., arching action is assumed to be present and the dead and the live
              loads are transferred to the adjacent masonry through the arching action; no part of
              this load is carried by the lintel. On the other hand, if the floor or the roof line lies
              below this height, the load from the wall must be carried as a uniform load by the
              lintel distributed over the entire span (Fig. 4.22b). In addition, there may be loads
              distributed uniformly only on a portion of the span.
           b. Concentrated load
                A method for determination of dispersion/distribution of concentrated loads on
              walls is recommended by NCMA [4.14] and BIA [4.15], which is based on test
              results reported in the literature [4.16, 4.17].
           Reference 4.16 reports results of tests on a wide variety of specimens subjected to con-
         centrated loads, including both concrete block and clay brick masonry, and AAC masonry.
         It suggests that a concentrated load can be dispersed at a 2:1 slope, terminating at half
         the wall height (measured from the point of application of the load to the wall footing
         (Fig. 4.25). In another study [4.16], tests on load dispersion through a bond beam on top
         of hollow masonry resulted in an angle from horizontal of 59° for a one-course CMU bond
         beam, 65° for a two-course CMU bond beam, and 58° for a two-course clay brick bond
         beam, or approximately a 2:1 slope [4.16]. Accordingly, for simplicity in design, a 2:1 slope
         is used for all cases of load dispersion of a concentrated load. Figure 4.25a shows disper-
         sion of a concentrated load (to be always supported on a bearing plate) through a bond beam
         for both running bond and stack bond. Figure 4.25b illustrates the effective length of a wall
         over which a concentrated load is assumed to be dispersed.


































         FIGURE 4.25  Load distribution on lintel due to concentrated loads.
   217   218   219   220   221   222   223   224   225   226   227