Page 278 - Design of Solar Thermal Power Plants
P. 278

260              4. DESIGN OF THE CONCENTRATION SYSTEM






























            FIGURE 4.22  Data record sheet of tracking deviation correction at the Badaling solar
            thermal tower power plant.

               and press the CONFIRM button to start the deviation correction
               process; at this time, the screen displays “deviation correcting.” After
               deviation correction starts, the heliostat goes into the mode of
               “executing . moving todeviation correction point” (refer to Fig. 4.23).
                  When the deviation correction point is reached, the current mode
               displays “deviation correction point reached”; the operator then
               initiates the CCD image acquisition camera while waiting for the
               image processing and analyzing system to return the deviation
               angle. As shown in Fig. 4.22, “horizontal deviation” and “vertical
               deviation” refer to the two deviation values from the white board
               center (unit: m).
                  To satisfy various working conditions, the range of deviation
               correction is adjustable by selecting the range through automatic
               or manual mode on the “System Maintenance” page. The manual
               mode can be modified on the “Deviation Correction Data Record”
               page; the range of the automatic mode can be automatically adjusted
               according to the solar field ring number where the heliostat has been
               located (distance from the heat-absorbing tower); the greater the
               distance, the greater the range for allowed deviation. Considering
               that deviation correction may not be completely adjusted to the
               white board center using the current setting, the maximum number
   273   274   275   276   277   278   279   280   281   282   283