Page 91 - Electrical Equipment Handbook _ Troubleshooting and Maintenance
P. 91

TRANSFORMER COMPONENTS AND MAINTENANCE

            4.20                       CHAPTER FOUR


                        40
                                                 A
                                Good
                        35      oil

                        30       Prop A
                      Interfacial tension, dynes/cm  25  Bad oil  Extremely  Oil in
                                  Marginal oil


                        20
                                       Very
                                       bad oil
                        15
                                                           condition
                        10                      bad oil    disastrous
                                B
                         5

                         0
                              0.2  0.4  0.6  0.8  1.0  1.2  1.4  1.5
                              Neutralization number, mg KOH/gram of oil
                     FIGURE 4.12 Plot shown was developed from the results of more than
                     10,000 IFT/NN tests. If a plot of IFT versus NN for a given oil sample does
                     not fall within the range shown on either side of the median line (as in the
                     case of points A and B), further investigation is in order. Additional tests (see
                     Table 4.2) should be conducted. The results should be evaluated in combina-
                     tion to get a true picture of the condition of both the oil and the transformer.

              Many separate reclamation/desludging treatments are needed if the transformer is in
            extremely sludged condition (NN   1.5). It is recommended to consider replacing the
            transformer at this stage. Reclamation/desludging should be performed before NN exceeds
            1.5 and IFT drops below 24.0, to ensure adequate operation and minimum deterioration of
            the insulation. The oil can be reclaimed/desludged while the transformer is online (ener-
            gized and in service) by properly equipped maintenance contractors. Therefore, there is no
            reason to allow the oil to deteriorate until an expensive treatment is required.
              It is essential to have adequate cleanliness and quality control while obtaining the test
            results. Dirty containers or laboratory equipment should not be used for the oil sample. It
            is very important to protect the sample from light, air, and moisture. The sample should be
            taken quickly, sealed in a container, and tested within hours. It must not be exposed to sun-
            light. Aging will accelerate if the sample is exposed to sunlight. The results of the sample
            could be misleading in this case.


            Gas-in-Oil
            The analysis of dissolved combustible gases in transformers is highly indicative of possi-
            ble trouble. All transformers will develop a certain amount of gases over their lifetime. The
            two principal causes of gas formation within an operating transformer are thermal and elec-
            trical disturbances. Heat losses from the conductors produce gases from decomposition of


         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   86   87   88   89   90   91   92   93   94   95   96