Area classification practice for dusts  159

































                                              Ground

                  Fig. 6.1  Cyclone and bag filter. x = 1.5 m, y = 1.5 m, z = 2 m


                                                 Roof







                           Wall                                          Wall














                  Fig. 6.2  Manually loaded hopper without  air  purge inwards through manhole in a
                         building.  X = 1.5 m.  Notes: (1) The  area  below  loading floor  level  is not
                         addressed. (2) Where air is drawn into the hopper through the manhole, the
                         dust cloud producing the Zone 21 will not exist provided airflow at manhole
                         mouth is at least 1 m/s inwards. (3) If housekeeping is sufficient to prevent
                         any layers forming the Zone 2 may be limited to 2-2.5  m around the hopper