Page 230 - Electrical Installation in Hazardous Area
P. 230

194  Electrical installations in hazardous areas

                                      No conducting framework








                                                        I
                                                        I
                                                        I
                                                        I








                                   Maximum area of each of  six external surfaces
                                   IIA and llB = 100 cm2
                                   IIC = 20 cm2
                                   Maximum volume
                                   IIA and 118  = 1000 cm3
                                   IIC = 90 cm3

                                     Conducting exposed earthed framework





















                                   Maximum area of each of six external surfaces
                                   IIA and llB = 400 cm2
                                   IIC = 100 crn2
                                   Maximum volume
                                   IIA and 118  = 8000 cm3
                                   IIC = 1000 crn3
                      Fig. 8.2  Insulating plastics enclosures