Page 41 - Electrical Installation in Hazardous Area
P. 41

20  Electrical installations in hazardous areas





                                 Applies to an approved       Operates a similar
                               (notified) body for certification  -OR   quality system of
                                  of production quality     1  own responsibility
                               system to BS/EN/OSI 9002             .c
                                         J-                  The approved (notified)
                                                               body examines and
                                 The approved (notified)       tests all equipment
                                body certifies the quality        produced








                                    For category 2 equipment (that intended for Zone 1)

                                  Applies to approved
                                  (notified) body for           system of own
                                  certification of his
                                  quality system to
                                   BSIENIISO 9003

                                                              body examines all
                                Approved (notified) body
                                 monitors quality system
                                     and product

                     Fig. 1.6(b)  Route to certification - Directive 94/9/EC


                     This will give more confidence to the user that purchases will accurately
                     reflect the certification but,  as the  quality management requirements are
                     again extremely subjective, it will cause considerable interpretive problems
                     and  is a  further need  for  an expanded HOTL.  The route to certification
                     under the new Directive is given in Fig. 1.6a. When the manufacturer has
                     obtained a type certificate for a product, using the system in Fig. 1.6a in
                     accordance with the appropriate EN Standard or the essential requirements
                     of  the Directive, the steps illustrated by Fig. 1.6b are followed in respect of
                     category 1 and category 2 equipment. (For category 3 equipment (intended
                     for Zone 2)  no certification by an approved (notified) body is necessary,
                     The manufacturer confirms compliance by declaration and application of
                     CE Mark.)


                     Ref e re n ces

                     1  Hicks, W. F and Brown, K. J (1971). Assessment of explosion probability
                        for intrinsically safe apparatus. (IEE Conference on electrical safety in
                        hazardous environments - 16-18  March).
   36   37   38   39   40   41   42   43   44   45   46