Page 202 - Estimators Piping Man Hour Manual
P. 202
Section Four—MECHANICAL INSTRUMENTATION 185
FLOW INDICATING TRANSMITTERS, FLOW RECORDERS,
AND FLOW CONTROLLERS
MAN HOURS EACH
Mail Hours
Item Each
FTI Flow Indicating Transmitter (mercury-less type), D/P cell type.
Foxboro Model: 45P. Case: Rectangular. Mounting: Yoke. Scale:
l
Eccentric, 6-A" length. Output Signal: 3-15 psi. Meter Body & Covers:
Type 37, forged steel, cadmium-plated. Diaphragm: Stainless steel.
1
Differential Range: 0-50" to 0-200" of water. Connections: A" or '//';
top or bottom. With air filter-regulator set and mounting yoke.
FC Flow Indicating Controller, Direct Connected, D/P Cell Type.
Foxboro Model: 43AP-FA 4. Control Function: Proportional plus
reset. Prop. Band: 4-400%. Reset Time: 0.5-25 minutes. Meter Body
& Covers: Type 37 forged steel, cadmium-plated. Differential Range:
0-50" to 0-200" of water. Scale: Eccentric. Ready Action: Reversible.
Set Point Knob: Internal. Output Gauge: 0-30 psi. Mounting: Yoke.
Connections: 54" or W; top or bottom. With air filter-regulator set
and mounting yoke.
PR Flow Recorder, Direct Connected, D/P Cell Type. Foxboro
Model: 40PR. Case: Rectangular. Mounting: Yoke. Pen: One, V-type.
Chart Drive: Electric, 115 volts, 60 Hz, 24-hour. Meter Body & Covers:
Type 37, forged steel, cadmium-plated. Differential Range: 0-50" to
1
0-200" of water. Connections: A" or W; top or bottom with
mounting yoke.
Above man hours include checking out of storage, calibrating, hauling to erection site, installing, testing and final
check.
Man hours do not include connections to process air supply and air signal lines. See piping account for mechanical
man hours. See Electrical Man Hour Manual for electrical charges.