188    Section  Four—MECHANICAL INSTRUMENTATION

         CONNECTING       PNEUMATIC PANEL BOARD            INSTRUMENTS


                                   MAN HOURS EACH


                                                                   Man Hours
                              Description                            Each
        Recording Controller— large case 12" circular  chart, with automatic reset,
                      one pen, one controller                         4,4
                      two pens,  one controlling,  one recording only  6.6
                      two pens, two controllers                       8.8
                      three pens, two controlling, one recording only  11,0
        Receiving Recorder— large case 12" circular chart,  one pen   2.7
                      two pens                                        3.3
                      three pens                                      5.0
        Receiving Indicator — concentric dial 3-/£" circular case
                      ribbon type, horizontal  or vertical  4" scale  1.7
                      ribbon type, for two variables                  3.3
        Manual Loading Station — 6" x 5-14" with circular dial and horizontal
          output indicator:
                      one pointer diaphragm  element                  2.2
                      two pointers  diaphragm element                 3.3
                      two pointers diaphragm element with set point
                       regulator                                      4.4
                      two pointers  diaphragm element with set point
                       regulator and auto ./man. unit                 5.0
                       l
        Recorder — 7-W  x  7-A",  4" strip  chart:, one  pen          2.2  ""
                      two pens                                        3.3
                      three pens                                      5.0
        Recording Control Station — 7-W  x  7-/4", 4" strip chart and vertical
          output gauge:
                      one pen                                         4.4
                      one pen, one pointer                            4.4
                      two peris                                       8.8
                      two pens, one pointer                           8.8
                      three pens                                      13.2
        Controller — Shelf Mounting: proportional  control            3.3
                      proportional  control  plus derivative  control  4.4
                      proportional control plus reset control         4.4
                      proportional control plus reset plus derivative control  4.4

      Above man hours include making tubing terminal connections,  calibrating,  checking, adjusting, testing, and commis-
      sioning pneumatic instruments.
      Mail hours for installation of air supply piping and air signal lines from control panel to remote instruments are not
      included. See other accounts for these man hours.
      No manufacturer's representatives are included in the above man hours.