SITE UTILITY SYSTEMS
36 4'3" 4'4" 4'7" 4'11" 5'3" 5'8" 6'0" 6'2" 6'8" 6'10" 7'4" 7'8" 7'11" 8'2" 8'6"
3'10" 4'1" 4'3" 4'6" 5'1" 5'5" 5'8" 6'1" 6'3" 6'5" 6'10" 7'2" 7'5" 7'9" 7'11"
33
30 3'7" 3'10" 3'11" 4'5" 4'8" 5'0" 5'5" 5'7" 5'10" 6'1" 6'5" 6'9" 7'0" 7'3" 7'5"
27 3'5" 3'6" 3'8" 4'1" 4'6" 4'8" 5'1" 5'3" 5'6" 5'7" 6'0" 6'3" 6'6" 6'8" 6'10"
24 3'1" 3'3" 3'5" 3'9" 4'1" 4'5" 4'8" 4'10" 5'0" 5'2" 5'5" 5'8" 5'11" 6'1" 6'2"
21 2'9" 2'11" 3'2" 3'6" 3'10" 4'1" 4'4" 4'6" 4'7" 4'9" 5'0" 5'3" 5'5" 5'6" 5'8"
Nominal pipe size, in 20 18 2'8" 2'5" 2'10" 2'8" 3'0" 2'10" 3'4" 3'1" 3'8" 3'5" 3'11" 3'8" 4'1" 3'10" 4'3" 4'0" 4'5" 4'1" 4'6" 4'3" 4'10" 4'5" 5'1" 4'7" 5'2" 4'9" 5'4" 5'0" 5'7" 5'2"
16 2'3" 2'5" 2'7" 2'11" 3'2" 3'4" 3'6" 3'7" 3'9" 3'11" 4'0" 4'2" 4'5" 4'7" 4'9"
15 2'2" 2'4" 2'6" 2'10" 3'1" 3'2" 3'4" 3'6" 3'7" 3'8" 3'10" 4'0" 4'3" 4'5" 4'6"
14 2'1" 2'3" 2'5" 2'8" 2'11" 3'1" 3'2" 3'3" 3'5" 3'6" 3'7" 3'11" 4'0" 4'3" 4'4"
Transition Width for Trenches 12 10 1'11" 1'9" 2'0" 1'10" 2'3" 1'11" 2'5" 2'0" 2'7" 2'2" 2'9" 2'5" 2'10" 2'5" 2'11" 2'6" 3'0" 2'8" 3'1" 2'9" 3'4" 3'0" 3'5" 3'1" 3'8" 3'2" 3'10" 3'3" 4'1" 3'5"
TABLE 6.9 Cover over top of pipe * 2'0" 2'6" 3'0" 4'0" 5'0" 6'0" 7'0" 8'0" 9'0" 10'0" 12'0" 14'0" 16'0" 18'0" 20'0" * 1 ft = 0.3 m.
6.53