SITE UTILITY SYSTEMS





                                  Velocity  ft/s  1.3  1.8  2.9  4.0  1.7  2.4  3.7  5.3  2.0  2.8  4.5  6.3  1.8  2.5  3.1  3.6  4.0  4.4  4.7  5.0  5.6  6.1  6.6





                               Full   cfs  0.03   0.04   0.06   0.09   0.08   0.11   0.18   0.25   0.17   0.25   0.39   0.55  0.35  0.49  0.60  0.70  0.78  0.86  0.92  1.00  1.10  1.20  1.30

                                  Discharge  gpm    13     18     28     40     36     51     80   114     77   110   174   245  157  220  269  314  350  386  413  449  494  539  583





                                  Velocity  ft/s  1.5   2.0   3.2   4.5   1.9   2.7   4.1   5.9   2.2   3.1   5.0   7.1  2.0  2.8  3.5  4.0  4.5  4.9  5.3  5.6  6.3  6.8  7.4




                               2/3 Full *   cfs  0.02   0.03   0.05   0.07   0.06   0.09   0.14   0.20   0.13   0.20   0.31   0.44  0.28  0.39  0.47  0.55  0.62  0.68  0.73  0.79  0.87  0.95  1.03



                                  Discharge  gpm    10     14     22     32     29     41     64     90     61     87   138   194  124  174  213  248  277  305  327  355  391  426  461





                                  Velocity  ft/s  1.3   1.8   2.9   4.0   1.7   2.4   3.7   5.3   2.0   2.8   4.5   6.3  1.8  2.5  3.1  3.6  4.0  4.4  4.7  5.0  5.6  6.1  6.6




                               1/2 Full    Discharge  cfs  0.02   0.02   0.03   0.05   0.04   0.06   0.09   0.13   0.09   0.13   0.20   0.28  0.18  0.25  0.30  0.35  0.39  0.43  0.46  0.50  0.55  0.60  0.65





                         Drainage Pipe Sizing Tables Discharge of circular sewer N = .013  gpm  %      7   1.0       9   2.1     14   4.2     20   8.3     18   1.0     26   2.1     40   4.2     57   8.3     39   1.0     55   2.1     87   4.2   123  8.3  79  0.5  110  1.0  135  1.5  157  2.0  175  2.5  193  3.0  207  3.5  225  4.0  247  5.0  270  6.0  292  7.0










                         TABLE 6.26                          Grade   Inch  Pipe  per  size,  foot  in  1/8    2   1/4       1/2       1      1/8    3   1/4       1/2       1      1/8    4   1/4       1/2       1  6  1/8  1/4  3/8  1/2  5/8  3/4  7/8