            TABLE 1.4  Problems and Possible Solutions in Pressure and Level Measurements
            Variable             Symptom                      Problem Source                 Possible Solution
            Pressure   Zero shift, air leaks in signal lines  Excessive vibration from positive  Use independent transmitter, flexible
                                                         displacement equipment         connection lines. Use liquid-filled
                                                                                        gauge
                       Variable energy consumption under  Change in atmospheric pressure  Use absolute pressure transmitter
                         temperature control
                       Unpredictable transmitter output  Wet instrument air           Mount local dryer, use regulator with
                                                                                        sump, slope air lines away from
                                                                                        transmitter
                       Permanent zero shift            Overpressure                   Install pressure snubber for spikes
            Level      Transmitter does not agree with level  Liquid gravity changes  Gravity compensate measurement or
                                                                                        recalibrate
                       Zero shift, high level indicated  Water in the process absorbed by  Use transmitter with integral remote
                                                         glycol seal liquid             seals
                       Zero shift, low level indicated  Condensable gas above liquid  Heat trace vapor leg. Mount trans
                                                                                        mitter above connections and
                                                                                        slope vapor line away from
                                                                                        transmitter
                       Noisy measurements, high level  Liquid boils at ambient temperature  Insulate liquid leg
                         indicated



               . What is the optimum liquid level in a stirred tank  . What are the common problems involved in pressure
                reactor?                                             and level measurements? Give suitable solutions.
                 & Liquid level ¼ tank diameter. It should be noted that  & Table 1.4 briefly gives the problems and solutions in
                  tank diameters are smaller at high pressures.        pressure and level measurements.