Rishel_CH08.qxd 21/4/06 6:16 PM Page 237
The Use of Water in HVAC Systems
The Use of Water in HVAC Systems 237
230
Building pump shut-off head 227 ft.
building pressure or 98 psig
210
Building hydraulic gradient
190
Building pump - 60 ft. head
170
System head (ft.) 150 Loss across
Return valve
130
96.0' return valve
41.6 psi
110 Coil furthest
from the plant
90
70
50
Chilled water distribution system (no scale)
Figure 8.10 Hydraulic gradient for figure 8.9. (From Patterson Pump
Company, HVAC Pumps and Systems Manual, 2004.)
Closed systems utilize external pressure to maintain the desired
operating pressure. This is accomplished through the use of makeup
water that is fed through a pressure regulator. Since they are closed
systems, they have an expansion tank to accommodate thermal expan-
sion and contraction caused by changes in system water temperature.
Following is a similar listing for closed systems described in this book.
Chillers and their pumps Chap. 14
Chilled water systems Chap. 15
Closed condenser water systems Chap. 16
Closed thermal storage systems Chap. 17
District heating and cooling Chap. 18
Hot water boilers Chap. 19