Page 235 - HVAC Pump Handbook
P. 235

Rishel_CH08.qxd  21/4/06  6:16 PM  Page 232




                                       The Use of Water in HVAC Systems

                    232   The HVAC World

                      Adding Tables 8.3 and 8.4 together into Table 8.5 gives the total
                    energy effect that the three coil and valve arrangements will have on
                    a chilled water system. It is obvious from this table that by far the
                    two-way valve without a circulator is the most efficient arrangement
                    of cooling coils and their control valves.
                      Tables 8.3 through 8.5 demonstrate the great variation of energy
                    caused by the various coil and control-valve arrangements. It must be
                    remembered that these tables were computed using specific chiller
                    and boiler efficiencies. A comparison of actual coil and valve arrange-
                    ments requires the determination of these efficiencies.
                      Table 8.6 lists wire-to-shaft efficiencies used in the above calculations
                    that were provided by a manufacturer of variable-frequency drives.
                      It should be pointed out that systems that are constantly loaded can
                    utilize three-way valves with some energy savings. Most HVAC water
                    systems, however, have variable loads due to building occupancy, light-
                    ing and machine loads, and variable outdoor air conditions.
                      These calculations should put to rest the use of three-way valves or
                    circulators on most coils on variable-volume hot and chilled water
                    systems. Much of this comparative information is 10 years old. Recent
                    studies have demonstrated that the energy consumption of constant-
                    speed pumps with manual balancing valves is as much as three times
                    the energy needed to operate the same system with variable-speed
                    pumps and automatic control of pump speed and without balance
                    valves. There are specific uses of circulators on coils to eliminate lami-
                    nar flow and freezing conditions; Fig. 8.7 describes this use. It should
                    be noted that the circulator is in the bypass, so it does not run except
                    when there are low loads on the coil. Usually, its motor is one-third to
                    one-quarter the size of a circulator installed on the supply connection
                    to the coil, as shown in Fig. 8.7. For elimination of freezing possibili-
                    ties, the circulator can be programmed to run whenever the outdoor
                    temperature is below 32°F and/or the load on the coil is at some dis-
                    creet level such as 70 percent.


                    TABLE 8.6 Wire-to-Shaft Efficiencies for Variable-
                    Speed Calculations

                     Percent speed   25-hp motor  30-hp motor
                          40            58            61
                          50            70            72
                          60            79            80
                          70            84            84
                          80            87            87
                          90            89            89
                         100            90            90





                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   230   231   232   233   234   235   236   237   238   239   240