Page 231 - HVAC Pump Handbook
P. 231

Rishel_CH08.qxd  21/4/06  6:16 PM  Page 228




                                       The Use of Water in HVAC Systems

                    228   The HVAC World

                    8.3.3 Contemporary two-way valve connection
                    The ability to evaluate more accurately the pressure drops that could
                    occur across control valves has resulted in the selection of valves bet-
                    ter fitted to a specific application. This has culminated in use of the
                    two-way valve directly connected to its coil and the supply and return
                    headers (see Fig. 8.5c). With proper calculation of maximum possible
                    pressure drop across the valve, the valve and its actuator can be sized
                    to operate under these pressures without damage or lifting of the
                    valve head off the valve seat.


                    8.3.4 Energy evaluations for three different
                    coil connections
                    Following are energy analyses using these three coil and control-valve
                    connections. This energy audit should demonstrate the need to elimi-
                    nate three-way valves and coil circulators on most variable-volume
                    systems. Circulators in coil bypasses do have specific uses on existing
                    systems, and these will be demonstrated in this chapter.
                      It is difficult to locate the right place in this book for the following
                    energy discussion. This is so important that it must be addressed
                    before specific installations are reviewed. Chapter 9 will develop the
                    primary/secondary pumping systems that were used with the older
                    coil circulator and three-way valve installations shown in Fig. 8.6a
                    and 8.6b. Variable primary pump will also be described there; it is




                                          3–constant speed pumps
                                          1000 GPM EA. @ 84 ft.
                                                   Supply header loss = 25 ft.
                    8 ft. loss
                    across pump
                    fittings
                                                             Ten
                    From                                     coils
                    chillers                  Coil              26 Ft. loss
                                                                across coil,
                    Chiller
                    loop bypass                                 valve, and
                                                                  piping

                                                   Return header loss = 25 ft.
                    To chillers
                    a. Secondary chilled water system with three-way control valves.
                    Figure 8.6  Water systems with the three coil connections.




                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   226   227   228   229   230   231   232   233   234   235   236