Page 229 - HVAC Pump Handbook
P. 229

Rishel_CH08.qxd  21/4/06  6:16 PM  Page 226




                                       The Use of Water in HVAC Systems

                    226   The HVAC World

                    sized with a low velocity in the tubes and low friction loss, laminar
                    flow develops and excessive water flow results. The designer must
                    balance the selection of coils between high water pressure loss and
                    laminar flow. The flow of water in the coil should not pass into the
                    laminar range at any known load on the coil.
                      How well we use hot or chilled water will determine the efficiency
                    of operation of the entire water system. Hot and chilled water systems
                    are described together here, because there is so much similarity
                    between hot water and chilled water coils in their use and in their
                    connections.
                      Hot and chilled water coil connections must be studied in detail to
                    ensure that the supply water is being used efficiently. There are a
                    number of ways to connect these coils, and many are being advocated
                    in the HVAC industry. Some of them are being sold to solve a particu-
                    lar system problem.
                      The system problems that are being addressed with these connec-
                    tions are:

                    1. Laminar flow in coils
                    2. Dirty coils—water side, air side, or both
                    3. Improperly sized coil control valves or valve actuators
                    4. Poorly constructed control valves

                    8.3.1 Three-way valves for hot and chilled water coils
                    When three-way valves were used predominantly on these coils, the
                    systems were constant flow, and there was little concern for energy
                    savings. The three-way control valve wastes energy by bypassing the
                    supply water around the coil, as shown in Fig. 8.5a. On variable-
                    volume chilled water systems, this has a negative effect on the
                    chillers, since the return temperature to the chillers is reduced. The
                    chillers reach rated water flow long before they achieve design load in
                    tons. This forces more than one chiller to operate when the cooling
                    load is less than the capacity of one chiller.

                    8.3.2 Two-way valve with circulator
                    Recognizing the deficiency of the three-way valve, efforts have been
                    made to control the return water temperature by replacing the three-
                    way valve with a two-way valve using a circulator on the coil (see
                    Fig. 8.5b). Laminar flow was eliminated with this arrangement, but
                    dirty coils could still pass water through the control valve below
                    design temperature on chilled water systems. The significant defect of
                    this arrangement is the continuous operation of the coil pump whenever




                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   224   225   226   227   228   229   230   231   232   233   234