Page 273 - HVAC Pump Handbook
P. 273

Rishel_09.qxd  20/4/06  6:34 PM  Page 270




                                       Configuring an HVAC Water System

                    270   The HVAC World

                    2. There is a danger that warm return water will be bypassed through
                       the crossover bridge back to the supply side of a coil that is fully
                       loaded and needs design supply temperature at that moment. The
                       result is that the coil will not supply the load required of it. For
                       example, in Fig. 9.12b, the fully loaded coil no. 5 needs 44°F water
                       to produce 10 tons of cooling; since it is receiving 50°F water, it can
                       produce only around 5 tons of cooling.
                    3. If certain coils are exhibiting laminar flow, circulating pumps can be
                       installed on the coils to avert this problem, as described in Fig. 8.4.
                       This is an excellent method for controlling laminar flow in a heating
                       coil. It was stated in Chap. 8 that, in most cases, pumps or circula-
                       tors should not be piped in series with the coil but in the bypass, as
                       shown in Fig. 8.7.
                    4. Return temperature-control valves obliterate the true return water
                       temperature from the system and prevent the operating and main-
                       tenance people from understanding which coils or control valves
                       are creating problems. Return temperature is the operator’s guide to
                       efficient use of water in HVAC systems.
                    5. Return water temperature control lulls maintenance people into
                       believing that there is no problem with any of their coils when
                       some of those coils may be very dirty on the air or water side.
                      In conclusion, one of the designer’s most important tasks is the
                    selection of a sound temperature differential that will provide
                    maximum possible system efficiency. The second step in this
                    process is to ensure that differential is maintained after the system
                    is commissioned.



                    9.10 Heat Exchangers for Hot
                    and Chilled Water

                    High-rise buildings, as shown in Fig. 9.12b, can create static pressure
                    problems on water systems where the remainder of the system is low
                    rise. The answer to this problem, often, is the use of a heat exchanger,
                    as shown in Fig. 9.13. The heat exchanger eliminates the static pres-
                    sure of the tall building from the water system pressure. The supply
                    temperature to the building is controlled by the supply control valve. If
                    this is a critical load or at the highest pressure loss of the system, a dif-
                    ferential pressure transmitter should be connected across the supply
                    side of the heat exchanger to ensure that adequate water is available to
                    the building at all loads on it.






                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   268   269   270   271   272   273   274   275   276   277   278