                                       Configuring an HVAC Water System

                                                    Configuring an HVAC Water System  271




                                                                     T
                     From pumps
                                                                         To
                                                                       building
                      To pump                  ∆P
                    speed control

                      To pumps
                                                                      Building
                                                                       pump
                    Locate differential pressure
                    transmitter for system
                    pumps if this  is a critical
                    building or at the point
                    of highest pressure loss
                    in system.
                    Figure 9.13  Heat exchanger for high risk building. (From Patterson Pump
                    Company HVAC Pumps and Systems Manual, 2004.)

                      One of the concerns for the control valve of Fig. 9.13 is the great loss
                    that may be incurred in it at light loads on the building. Through
                    adaptive control, the set point for the differential pressure transmitter
                    can be reset on light loads through a valve position indicator/transmitter
                    on the control valve as per Fig. 9.14. The differential pressure across



                      Valve position indicator-
                      transmitter
                      To pump speed
                      control                                        T

                      From pumps                                         To
                                                                       building
                      To pump                  ∆P
                      speed control

                      To pumps
                                                                      Building
                                                     Heat exchanger
                                                                       pump
                      Set point is adjusted by
                      valve position to hold
                      valve to 80 to 85 % open
                    Figure 9.14 Valve position control on heat exchanger.