Page 279 - HVAC Pump Handbook
P. 279

Rishel_CH10.qxd  21/4/06  6:20 PM  Page 276




                                   Basics of Pump Application for HVAC Systems

                    276   The HVAC World
















































                    Figure 10.2 Pump operation with system head area.




                    and then pick the pump to the left of the best efficiency point to ensure
                    that the pump will operate without damage at the higher flows and
                    lower heads. The other practice has been to install a balancing valve
                    on the pump discharge, either manual or automatic, and add enough
                    friction to prevent some of the operation at higher flows. One of the
                    advantages of variable-speed pumps is that this “carryout” condition is
                    eliminated by their controls without all the inefficiencies of pump
                    head conservation factors and balancing valves.





                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.