Rishel_CH10.qxd 21/4/06 6:20 PM Page 281
Basics of Pump Application for HVAC Systems
Basics of Pump Application for HVAC Systems 281
88
87
86
Pump efficiency—% 85
84
83
82
81
80
800 900 1000 1100 1200
Pump speed—RPM
Figure 10.5 Pump effiency during constant flow, variable
head process.
possible efficiencies. Multispeed head-flow curves should be secured
from the pump manufacturer, and the actual proposed operation
should be drawn on them. Another example of a proposed variable
flow, variable head operation is shown in Fig. 10.6 which is an exam-
ple of mapping the variable-speed pump performance.
80 1180 RPM
70% 75% 80% 83%
60 1000 RPM 86% 87% Bep curve
Pump head—ft. 40 800 RPM 83%
86%
Individual
efficiency
20 lines of
0
0 400 800 1200 1600 2000 2400 2800 3200
U.S. Gallons per minute
Figure 10.6 Variable flow, variable head process.